Safety Precautions - Panasonic CZ-256ESMC3 Manual Del Usuario

Ocultar thumbs Ver también para CZ-256ESMC3:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 7
ENGLISH

Safety Precautions

Please Read Before Starting
This controller must be installed by the sales dealer or installer.
These instructions are all you need for most installation sites
and maintenance conditions. If you require help for a special
problem, contact our sales/service outlet or your certifi ed dealer
for additional instructions.
This symbol refers to a hazard or unsafe
WARNING
practice which can result in severe personal
injury or death.
This symbol refers to a hazard or unsafe
CAUTION
practice which can result in personal injury
or product or property damage.
 We assume no responsibility for accidents or damages
resulting from methods other than those described in the
installation instructions or methods without using specifi ed
parts. Malfunctions that occurred due to the unauthorised
installation methods are not covered by the product warranty.
 This controller shall be installed in accordance with National
Wiring Regulations.
 After the installation is complete, perform test operation to
confi rm that no abnormality is present.
 Read the installation instructions of devices to be connected as well.
 When relocating or repairing this controller, provide the
Installation Instructions to the servicing personnel.
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO WIRE
THIS SYSTEM.
 Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and
these instructions when wiring.
Improper connections and inadequate grounding can
cause accidental injury or death.
 This controller is strongly recommended to be
installed with Earth Leakage Circuit Breaker
(ELCB) or Residual Current Device (RCD).
Otherwise, it may cause electrical shock and fi re
in case of equipment breakdown or insulation
breakdown.
Earth Leakage Circuit Breaker (ELCB) must be
incorporated in the fi xed wiring in accordance with
the wiring regulations. The Earth Leakage Circuit
Specifi cations
Model No.
CZ-256ESMC3
Dimensions
240 × 280 × (20 + 65) mm
[H × W × D]
Weight
2.7 kg
Temperature/
0 °C to 40 °C / 20 % to 80 %
Humidity range
(no condensation) Indoor use only.
Rated voltage/
Single phase 100-240 V ~ 50/60 Hz
Rated frequency
Power consumption Max. 20 W
*1: The maximum number of connectable units is shown below.
• When using only this unit: 128 indoor units and 60 outdoor units
• When connecting a Communication Adaptor: 256 indoor units and 120 outdoor units
WARNING
Breaker (ELCB) must be an approved 10 A, having
a contact separation by 3 mm in all poles.
 Provide a power outlet to be used exclusively for
this controller.
 Turn off the circuit breaker of the controllers
before installation.
 Do not supply power to the controller until all wiring is
completed or reconnected and checked.
 Fix the power supply wiring securely with the
clamper so that the power supply terminal board
is free of tension (external force) when pulled.
Loose connection of the terminal board may
cause fi re.
 To prevent possible hazards from insulation
failure, the controller must be grounded.
 Select an installation location which is rigid and
strong enough to support or hold the controller, and
select a location for easy maintenance.
 This product must not be modifi ed or
disassembled under any circumstances.
Modifi ed or disassembled controller may cause
fi re, electric shock or injury.
 Do not clean inside the controller by users.
Engage authorized dealer or specialist for cleaning.
 Do not operate with wet hands.
 Ground yourself to discharge static electricity
before performing any wiring.
 Do not use the controller at the following locations.
• Areas where leakage of fl ammable gas may be
expected
• Places where large amounts of oil mist exist
• Locations where external air may enter the room
directly (This may cause "condensation")
• Locations where high-frequency emissions are
generated
• Locations where voltage fl uctuation frequently occurs
 Do not wash with water.
NOTICE
The English text is the original instructions. Other languages are
translation of the original instructions.
± 30 seconds/month (at normal temperature 25 ˚C)
Precision
* Adjust periodically.
Clock
Holding
100 days (at normal temperature 25 °C with full charge)
time
* Approx. 8 hours are required for full charge.
Up to 100 units of the combined total of the
Number of
following
connectable
• Indoor unit - Up to 64 units*
units per link
• Outdoor unit - Up to 30 units
*1
• Central control device - Up to 10 units
*2: The number of indoor units includes the
Interface Adaptor.
2
CAUTION
2

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido