Wire connection
REQUIREMENT
• Be sure to connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
• Be sure to pass the cables through the bushing of wiring connection port of the indoor unit.
• Keep a margin (Approx. 100mm) on a wire to hang down the electric parts box at servicing, etc.
• Remove the cover of the electric parts box by taking off the mounting screws (3 positions) and pushing the hooking section. (The
cover of the electric parts box remains hanged to the hinge.)
• Connect the indoor/outdoor connection wires to the terminal block of the electric parts box. (Do not apply tension to the connecting
section of the terminal block.)
• Tighten the screws of the terminal block, and fix the wires with cord clamp attached to the electric parts box. (Do not apply tension
to the connecting section of the terminal block.)
• Using the attached thermal insulation material, seal the pipe connecting port. Otherwise, dewing may be caused.
• Mount the cover of the electric parts box without pinching wires. (Mount the cover after cabling on the ceiling panel.)
Screws
P.C. board
Earth screw
Cord clamp
Wiring on the ceiling panel
According to the Installation Manual for the ceiling panel, connect the connectors
to the P.C. board in the electric parts box.
Connect the sensor connector to CN201 (Blue), and the louver motor wiring
connector to CN33 (White) on the P.C. board, respectively.
Draw and pass the sensor lead wire upper the louver motor wiring, and then
close cover of the electric parts box. Perform the wiring work so that the electric
parts box does not pinch the sensor lead wire.
Push
Screw
Power supply
Hooking
terminal block
section
Heat insulator B
Electric parts box
Thermal insulation to
wiring connecting port
Cover of electric
parts box
CN33
19
Adhered surface
Heat
insulator A
Notched section
Infrared signal receiver wiring
(From ceiling panel)
Louver motor wiring
(From ceiling panel)
Cord clamp
CN201
EN