Descargar Imprimir esta página

Frico ADEA Manual De Instrucciones página 27

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 59
using the SET button. Following this change,
the selected weekly programme is activated
to control the operating position for the
specified time settings.
To change a value, press the SET button
one or more times until the required value
starts to flash. Now make your changes using
the arrow keys. To activate a day of the week,
press the SET button repeatedly until the
relevant day flashes. Now press the up arrow
key. Press the down arrow key to inactivate
the day of the week.
Weekly programme number
Select active weekly programme,
1 or 2, 0=no weekly programme
Time setting 1
Connect day mode
Monday - Friday, 08:00
Time setting 2
Connect night mode
Monday - Friday, 18:00
Time setting 3
Connect day mode
Saturday, 09:00
Time setting 4
Connect night mode
Saturday, 16:00
Time setting 5
Connect day mode
Sunday, 11:00
Time setting 6
Connect night mode
Sunday, 16:00
ADEA
Heating regulation parameters
The heating regulation parameters control the
heating function.
The displays show the default settings for
the regulator's heating regulation parameters.
Change parameter values by pressing the
arrow keys until the required parameter is
displayed. Now press the SET button and
change the value using the arrow keys.
Save by pressing the SET button again. The
regulator will revert to showing the current
room temperature automatically after 30
seconds.
Outdoor temperature limit for
heating
When the outdoor temperature
sensor detects a temperature
higher than the set value, the
heating in the unit will not be
activated. This function overrides
all others.
Differential temperatures
between power stages
Power stage 1 will be used if the
desired value is 20°C and the
temperature is between 18°C
and 20°C. Power stage 2 will
be activated if the temperature
drops below 18°C. This only
applies when the door is closed,
i.e. the service heater function in
the entrance.
GB
27

Publicidad

loading