Description of 40VCBM17FQEE Modbus function
External of Modbus point list:
Object Name
Indoor1—40
Running mode
control
Indoor1—40
Temperature control
Indoor1—40
Fan speed
control
Indoor1—40
Temperature
Indoor1—40
Startand stop control
Indoor1—40
Error code
Address
40006—40045
40046—40085
40086—40125
40126—40165
40166—40205
40206—40245
9
Object Type
AO / AI
0 : Auto
1 : Fan
2 : Cool
3 : Dry
4 : Heat
An integer between
AO
16 to 30
0 : Auto
AO / AI
1 : Low
2 : Normal
3 : High
Minus 64 is
AI
Temperature
0 : OFF
DO / DI
1 : ON
0 : Normal
DI
1 : False
State Text
RW
R / W
W
R / W
R
R / W
R