Address Setting When Using Central Controller
Point table:
Point description
All On/All Off
Indoor unit (1-64)
ON/OFF setting
Indoor unit (1-64)
ON/OFF state
Indoor unit (1-64)
Malfunction state
Indoor unit 1 ON/
OFF setting
Indoor unit 1 mode
setting
Indoor unit 1
temperature
setting
Indoor unit 1 fan
speed setting
Indoor unit 1 ON/
OFF state
Indoor unit 1 mode
Indoor unit 1
temperature
setting
Indoor unit 1 current
fan speed
Indoor unit 1 current
temperature
Indoor unit 1 error
code
Protocol
Extra
address
address
40006
40011-
40014
0-15
40015-
40018
0-15
40019-
40022
0-15
40031
40032
40033
40034
40035
40036
40037
40038
40039
40040
14
Point
type
AO
(Write)
1:All On
DO
(Write)
1:ON
DI
(Read)
1:ON
DI
(Read)
1:Error 0:Normal
1:ON,0:OFF
0:Auto,1:Fan 2:
Cooling,3:Dry 4:Heating
Integer from 16 to 30
AO
(Write)
0:Auto,1:Low 2:
Medium,3:High
1:ON,0:OFF
0:Auto,1:Fan, 2:
Cooling,3:Dry, 4:Heating
1 to 16 represents
0:Auto,1:Low 2:
Medium,3:High
AI
Integer between - 20 and
(Read)
Integer from 0 to 150
State
0:All Off
0:OFF
0:OFF
16
C to
0
30
C
0
50I

Publicidad