Address Setting When Using Central Controller
Point description
Indoor unit 1
ON/ OFF state
Indoor unit 1 mode
Indoor unit 1
set temperature
Indoor unit 1
current fan speed
Indoor unit 1
current temperature
Indoor unit 1
error code
Indoor unit 2
ON/ OFF setting
Indoor unit 2
mode setting
Indoor unit 2 tem-
perature setting
Indoor unit 2
fan speed setting
Indoor unit 2
ON/ OFF state
Indoor unit 2 mode
Indoor unit 2
set temperature
Indoor unit 2
current fan speed
Indoor unit 2
current temperature
Indoor unit 2
error code
Protocol
Extra
address
address
40047
40048
40049
40050
40051
40052
40053
40054
40055
40056
40057
40058
40059
40060
40061
40062
20
Point
State
type
1:ON,0:OFF
0:Auto,1:Fan 2:
Cooling,3:Dry 4:Heating
1 to 16 represents
0:Auto,1:Low 2:
Medium,3:High
AI
(Read)
Integer between 20 and
50
Integer from 0 to 150
1:ON,0:OFF
0:Auto,1:Fan 2: Cool-
ing,3:Dry,
AO
Integer from 16 to 30
(Write)
0:Auto,1:Low 2:
Medium,3:High
1:ON,0:OFF
0:Auto,1:Fan 2: Cool-
ing,3:Dry,
1 to 16 represents
0:Auto,1:Low, 2:
Medium,3:High
AI
(Read)
Integer between 20 and
50
Integer from 0 to 150
16
C to
0
30
C
0
4:Heating
4:Heating
16
C to
0
30
C
0