Autochange. This option allows the user to configure the three values that define the auto-
changeover operation that sets the mode of the indoor unit.
o Setpoint Differential. Defines the minimum differential between heating and cooling set
points. Values: 0 to 3,5˚C / 0 to 7˚F, in steps of 0,5˚C / 1˚F (by default, 1˚C / 2˚F).
o Mode Switching Protection (min). Defines the minimum run time before allowing a
mode change. Possible values are 15, 30, 60 and 90 minutes. By default, 30 minutes.
o Heat OVR Temp. If a zone has a higher heating demand than this temperature, the
system reverts heating operation even if the cooling global demand exceeds the global heat
demand. Possible values are: Off, 1.5 to 4˚C / 3 to 8˚F in increments of 0.5˚C / 1 ˚F. Default
value: Off.
•
Room Temperature. This option allows the room temperature and relative humidity to be
shown/hidden. By default, the room temperature is shown.
•
Lite Step. This option configures the temperature increments. Values: 0.5 or 1˚C / 1 or 2 ˚F
(by default, 0.5˚C / 1 ˚F).
•
Reset system. (only available for master thermostat Blueface). Resets the system
and returns to factory settings. To reconfigure the thermostats, please check Initial
configuration).
•
Remote Assistance. This option enables/disables remote assistance. By default, remote
assistance is disabled.
ZONE PARAMETERS
•
Associated outputs. This displays and allows you to select the control outputs associated to
the thermostat.
•
Thermostat settings. This allows you to set up a thermostat as Master or Zone.
*Note: It cannot be configured as Master if there is already another thermostat configured
as such.
•
Use mode. This allows you to configure the thermostat for the system's different zones
in Basic or Advanced mode. By default, it is set to Advanced. The parameters that can be
controlled in Basic mode are:
- On/Off.
- Set-point temperature.
- Operation mode (only if this is the master thermostat).
- Fan speed.
If you need to reset the thermostat to Advanced mode, access the Advanced settings menu
and activate Advanced use mode.
•
Offset. This allows you to correct the room temperature measured in the different zones or
in all of them, due to deviations produced by sources of heat/cold nearby, with a correction
factor between -2.5°C / -5º F and 2.5°C / 5º F in steps of 0.5°C / 1º F. By default, it is set to 0°C/
32º F.
EN
19