12. If the output is required, select Output Enable.
13. Click Save to save changes.
14. If the output is required, click Output Program and select
the action to follow. The output will trigger when the action
is true.
15. Click Save to save changes.
Note on Tamper
Two rubber push buttons provide front case and rear wall
tamper.
To clear an Expander Tamper condition, both tamper inputs
must be sealed. The enclosure should be firmly mounted on a
flat surface with the cover closed.
If either tamper input is open then an Expander Tamper
condition will occur.
Note on Relay Modes
The receiver features one Single Pole Double Throw (SPDT)
Form C relay.
The relay is connected to output terminal J6 with Normally
Open and Normally Closed connections for your convenience.
D14 is a red LED that lights up when the relay is energized.
P/N 466-2948 • REV A • ISS 14DEC17
The relay can be configured in 3 different modes to support
different applications. Use jumper on J5 to select the mode
suitable for your requirements.
Jumper J5
Buss Voltage +
Common C
GND –
Default is no jumper with relay in NC position
No Jumper
Dry contact closure provided to output terminal. Maximum
Load 30VAC @ 1A or 30VDC @ 1A.
Jumper between - and C
Buss Ground provided to output terminal @ typical 0V. Do not
exceed relay rating which is maximum load 30VAC @ 1A or
30VDC @ 1A.
Jumper between C and +
Buss Voltage provided to output terminal @ typical 12-13VDC.
Maximum Load @ 12V is total panel current of 700mA, this
includes all connected codepads and expansion modules. Do
not exceed relay rating.
Adding Wireless Devices
1.
Log in to the xGen control panel.
2.
Click Settings.
3.
Select Zones in the drop down menu.
4.
Select the zone number you want to configure:
Output J6
NC
C
C
NO
O