6. Faults
WARNING!
Physical injuries and damage to property and the environment caused by hazardous media
Upon contact with hazardous media (e.g. oxygen) and also with refrigeration plants and compressors,
there is a danger of physical injuries and damage to property and the environment.
▶
EN
▶
▶
For contact details see chapter 1 "General information" or the back page of the operating instructions.
In the event of any faults, first check whether the pressure sensor is mounted correctly, mechanically and electrically.
If complaint is unjustified, the handling costs will be charged.
Fault
No output signal
No output signal
No/wrong output signal
Constant output signal upon change in
pressure
Deviating zero point signal
Signal span too small
Signal span too small
Signal span drops
16
All manuals and user guides at all-guides.com
Should a failure occur media with extremely high temperature and under high pressure or vacuum
may be present at the instrument.
For these media, in addition to all standard regulations, the appropriate existing codes or regulations
must also be followed.
Wear the requisite protective equipment.
Possible cause
Cable break
No/wrong power supply
Wiring error or switching of switching logic
Mechanical overload caused by overpres-
sure
Overload safety exceeded
Mechanical overload caused by overpres-
sure
Power supply too high/low
Moisture has entered
Measure
Check the continuity
Rectify the power supply
Observe the pin assignment
Check the output configuration
Replace instrument; if it fails repeatedly,
contact the manufacturer
Observe the permissible overload safety
Replace instrument; if it fails repeatedly,
contact the manufacturer
Rectify the power supply
Fit the cable correctly
WIKA operating instructions, pressure sensor, model A-1200