English
C 230 ECO : Setting the burner parameters
Press the
key until #CONFIGURATION is displayed.
Successively press
until #BOILER is displayed, then on
MAX.VENT., MIN.VENT. and ST.VENT. are displayed.
If the boilers are in cascade, press the
with K3 control panels.
The parameters can be modified with the + and - keys.
GSR 230 Condens: Setting the burner parameters
- Open the flap.
- Press the
key until #PARAMETERS is displayed.
- Turn the rotary button to select #CONFIGURATION. Press the
rotary button successively until MAX.VENT., MIN.VENT. and
ST.VENT. are displayed.
The parameters can be modified by turning the rotary button.
Access to these parameters is only possible one minute after
the appliance has been switched on and as long as no faults are
detected.
Setting value CO
- Propane (G31)
2
Low speed
Fan rotation speed
Boiler type
C230-85 ECO /
GSR 233 Condens
C230-130 ECO /
GSR 234 Condens
High speed
Fan rotation speed
Boiler type
C230-85 ECO /
GSR 233 Condens
C230-130 ECO /
GSR 234 Condens
03/07/08 - 300015337-001-A
key for the boilers fitted
CO
MIN.VENT.
rpm
%
1500
10.5 ±0.5
1400
10.5 ±0.5
CO
MAX.VENT.
rpm
%
5200
10.0 ±0.7
6100
10.0 ±0.7
C 230 ECO / GSR 230 Condens
Overpressure cascade combined with propane
(G31)
until
Low speed - Cascade with overpressure combusted gases
50-80 Pa
Boiler type
C230-85 ECO /
GSR 233 Condens
C230-130 ECO /
GSR 234 Condens
High speed - Cascade with overpressure combusted gases
50-80 Pa
Boiler type
C230-85 ECO /
GSR 233 Condens
C230-130 ECO /
GSR 234 Condens
Rotation at start-up - G31 and cascade de gaz brûlés à
2
surpression
Boiler type
C230-85 ECO /
GSR 233 Condens
C230-130 ECO /
2
GSR 234 Condens
Fan rotation speed
MIN.VENT.
rpm
50 Pa
80 Pa
1800
2000
1900
2100
Fan rotation speed
MAX.VENT.
rpm
50 Pa
80 Pa
5200
6100
Fan rotation
Fan rotation
speed
speed
ST.VENT.
ST.VENT.
0 Pa
50 Pa
rpm
rpm
2000
2200
2000
2300
CO
2
%
10.0 ±0.5
10.0 ±0.5
CO
2
%
10.0 ±0.7
10.0 ±0.7
Fan rotation
speed
ST.VENT.
80 Pa
rpm
2400
2500
7
7

Publicidad