Step 4 – Using
External
Instructions to change to
Follow instructions below to use digital input for start command.
Power down the drive, wait 5 min.
Make the connections as shown below in Fig. 2a.
Verify that all connections are secure and power-up the drive.
Set Par. F_10 "Main Run Source Selection" = 1: "External Run/Stop"
DANGER
Risk of electric shock
Touching blank or not connected wires/cables will result in electric shock and physical injury including the risk
of death.
Do not apply power until all connections are correct and secure and all protective covers are in place.
RA
R B +24V I1D
Digital
Input
Common
Step 5 – Using an external
Follow instructions below to use External Analog Input as setpoint reference.
Power down the drive, wait 5 min.
Make the connections as shown below in Fig. 2b.
Verify that all connections are secure, replace covers and power-up the drive.
Set Par. F_11 "Main Frequency Source Selection" = 2: "External AVI Analog Signal Input"
DANGER
Risk of electric shock
Touching blank or not connected wires/cables will result in electric shock and physical injury including the risk
of death.
Do not apply power until all connections are correct and secure and all protective covers are in place.
08/19
RUN/STOP
External Run/Stop
I2D
I3D
I4D
I5D
10V AVI ACI
Forward FWD
Start / Stop
Switch
(Maintained)

Analog Input

for speed control
Quick Start Guide S2U IP20
AO GND
Fig. 2a
Fig.2b
EN
3