Descargar Imprimir esta página

Wolf 10 Instrucciones De Servicio Para El Instalador página 8

Grupo de bomba solar

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 14
Flow regulation
Air separator
with vent valve
Start-up
Pressure drop characteristic
for solar pump assembly
(refer to page 38-39 for the pump
performance curve)
8
Operation instructions for contractors
GB
Solar pump assembly 10 / 20
- Connect the filling and flushing pump to the upper fill valve of the safety valve assembly
- Connect the hose to the drain valve of the flow regulator and feed it into the filling
container.
- Use a screwdriver to turn the gravity brake in the return branch (1) to the vertical
position
- Turn the ball valve (temperature display) in the feed branch (2) to the 45° position and
the ball valve in the return branch (1) to the 90° position. => no forced flow through
the solar circuit pump during filling and flushing.
Fill valve
- Fill the solar system slowly.
Gravity
- During the flushing procedure open the ball valve in the return branch (1) several
brake
times briefly in order to purge the air from the solar circuit pump.
- Open the vent valve on the air separator of the feed branch (2) until ANRO runs out.
- Close the drain valve, adjust the system pressure, close the fill valve and remove the
Set screw
flushing pump.
Drain valve
- Turn the gravity brake back to its initial position
valves in the feed and return branches back to the vertical position.
If the collector circuit is re-heated by the storage tank, the permissible operating
overpressure in the piping network between the storage tank and the pump as-
sembly may be exceeded!
- After the filling and flushing procedure, all ball valves in the solar station (feed and
return branch) and the adjusting screw on the flow regulator must be opened again!
- All ball valves must remain open during operation!
- The hot water storage (boiler) must be switched off for maintenance and repair work.
- Start the solar control unit
(see control system installation and service instructions).
- Set the solar circulation pump to continuous operation
(see control system installation and service instructions).
- Turn the adjusting screw of the flow regulator to the vertical position
- Set the speed of the solar circulation pump to the required flow rate at the speed
switch (rough setting).
- The recommended flow rate can be finely adjusted using the adjusting screw.
Flow rate:
- Check the system pressure and top up the system if necessary.
(open).
0.5 - 1.5 l/min per collector
High Flow:
1.5 l/min x collector
Low Flow:
0.5 l/min x collector
e.g. high flow: 2 collectors x 1.5 l/min = 3 l/min
Flow rate V in l/min
(automatic mode). Turn the ball
(max. flow rate).
3062498_201911

Publicidad

loading

Este manual también es adecuado para:

20Grupo de bomba solar 10Grupo de bomba solar 20