Instruction Leaflet IL040016EN
Effective January 2022
International cable and fuse sizes—208 Vac to 240 Vac ratings
Amp suffix
Frame
size
(CT/I
)
(VT/I
)
H
L
FR0
3D7
4D8
4D8
6D6
6D6
7D8
FR1
3D7
4D8
4D8
6D6
6D6
7D8
7D8
011
011
012
FR2
012
017
017
025
025
031
FR3
031
048
048
061
FR4
061
075
075
088
088
114
FR5
114
143
143
170
170
211
FR6
211
248
248
312
1
Line and motor cable size is selected according to IEC 60364-5-52:2009 Table B.52.4 for copper conductor with PVC insulation with a wiring
condition of ambient temperature 30 °C in air and an installation method of "B2" (cables in conduit and cable trunking systems).
For other wiring conditions, please refer to the standard of IEC 60364-5-52:2009 for suitable cable sizes.
2
Earthing conductor size is determined by the cross-sectional area of phase conductors according to IEC/EN 61800-5-1:2007 Table 5.
So if phase conductor size is changed, earthing conductor size should also be changed accordingly.
3
If power cubes or bypass are used, a Class gG/gL fuse is recommended.
16
EATON
www.eaton.com
208 V
input current
Current
(CT/I
)
H
(CT/I
)
(VT/I
)
at 50 °C
H
L
4.3
5.6
3.7
5.6
7.6
4.8
7.6
9
6.6
3.2
4.4
3.7
4.4
6.1
4.8
6.1
7.2
6.6
7.2
10.2
7.8
10.2
11.6
11
10.2
16.3
12.5
16.2
23.2
17.5
23.1
29
25
28.7
44.2
31
44.4
56
48
56.4
64.6
61
69.4
78
75
81.4
94.3
88
105.5
129
114
132.3
157
143
157.3
189
170
196.3
242.8
211
230.7
290.3
248
12
Fuse
Mains and
(VT/I
)
rating
motor cable
L
at 40 °C
(gG/gL)
3
Cu (mm
4.8
10
3*1.5+1.5
6.6
10
3*1.5+1.5
7.8
16
3*1.5+1.5
4.8
6
3*1.5+1.5
6.6
10
3*1.5+1.5
7.8
16
3*1.5+1.5
11
16
3*1.5+1.5
12.5
16
3*1.5+1.5
17.5
20
3*4+4
25
32
3*4+4
31
32
3*6+6
48
50
3*16+16
61
63
3*16+16
75
80
3*25+16
88
100
3*35+16
114
125
3*50+25
143
160
3*70+35
170
200
3*95+50
211
250
3*150+95
261
400
2*(3*70+35)
312
400
2*(3*95+50)
PowerXL DG1 Series VFD
Terminal cable size
Main terminal
Earth terminal
2
2
)
Cu (mm
)
Cu (mm
0.2–6 solid or
0.75–6
0.2–4 stranded
0.2–6 solid or
0.75–6
0.2–4 stranded
0.2–6 solid or
0.75–6
0.2–4 stranded
0.2–6 solid or
0.75–6
0.2–4 stranded
0.2–6 solid or
0.75–6
0.2–4 stranded
0.2–6 solid or
0.75–6
0.2–4 stranded
0.2–6 solid or
0.75–6
0.2–4 stranded
0.2–6 solid or
0.75–6
0.2–4 stranded
0.5–16
4–16
0.5–16
4–16
0.5–16
4–16
16–35
2.5–25
16–35
2.5–25
16–50
6–50
16–50
6–50
16–50
6–50
50–185
10–120
50–185
10–120
50–185
10–120
2*(50–150)
35–150
2*(50–150)
35–150
2
)