Eaton PowerXL DG1 Serie Instrucciones De Montaje página 5

Ocultar thumbs Ver también para PowerXL DG1 Serie:
Tabla de contenido

Publicidad

PowerXL DG1 Series VFD
Mounting—Montaje—Montage—Montage—Montaggio—Montering—Montering—Τοποθέτηση—Montagem—
Asennus—Montering—Montáž—Paigaldamine—Felszerelése—Montāža—Montavimas—Montaż—Montaža—
Montáž—Монтаж—Montarea—Montaža—Montaj—Монтаж— 安装 —Монтаж—
C
A
D
A
2
Frame
B
2
size
In (mm)
In (mm)
FR0
0
0
FR1
0.79
1.58
(40)
(20)
FR2
1.18
2.36
(60)
(30)
FR3
0
0
FR4
0
0
FR5
3.15
6.30
(160)
(80)
FR6
0
0
1
kW ratings are at 400 V / 50 Hz.
2
Minimum clearances A and B for drives with Type 12 (IP54) enclosure is 0 mm (in) for FR1, FR2, FR3, FR4, FR6.
3
The above guidelines apply unless testing has been completed to validate a design outside of these recommendations.
B
A
A
C
D
In (mm)
In (mm)
3.94
1.97
(100)
(50)
3.94
1.97
(100)
(50)
6.30
2.36
(160)
(60)
7.87
3.15
(200)
(80)
11.81
3.94
(300)
(100)
11.81
7.87
(300)
(200)
15.75
12.99
(400)
(330)
Cooling air
required
3
CFM (m
/h)
3
16.5
(28)
14
(24)
55
(94)
85
(144)
153
(260)
232
(395)
230 V: 435 (739)
460 V/600 V: 400 (679)
Instruction Leaflet IL040016EN
Effective January 2022
EATON
www.eaton.com
5

Publicidad

Tabla de contenido
loading

Tabla de contenido