PowerXL DG1 Series VFD
North America cable and fuse sizes—525 Vac to 600 Vac ratings
575 V input
575 V input
Frame
Amp
current
current
size
suffix
(CT/I
)
(VT/I
H
FR1
3D3
3.1
4.2
4D5
4.2
7
7D5
7
9.3
FR2
010
9.3
12.5
013
12.5
16.7
018
16.7
20.4
FR3
022
20.4
25.2
027
25.1
31.7
034
31.6
38.2
FR4
041
38.1
48.1
052
48.3
57.4
062
57.6
73
FR5
080
74.4
91.3
100
93
114.1
125
116.2
132.9
FR6
144
140.4
202.8
208
202.8
243.8
1
Line and motor cable size is selected according to UL 508C Table 40.3 for copper conductor rated 75 °C. Use only with copper wire rated 75 °C here.
Size requirements for other different wire types are defined in the National Electrical Code, ANSI/NFPA 70.
2
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL 508C Table 6.4.
3
If power cubes or bypass are used, a UL listed Class RK5, J, T or equivalent fuse is recommended.
NEC motor
Current
amp rating at
(CT/I
) at
H
)
575 V
50 °C
L
3.9
3.3
6.1
4.5
9
7.5
11
10
17
13.5
22
18
27
22
32
27
41
34
52
41
62
52
77
62
99
80
125
100
144
125
192
144
242
208
12
NEC wire
Size (AWG)
Current
(VT/I
) at
Recommended
Line and
L
40 °C
fuse rating
3
motor
4.5
10
14
7.5
10
14
10
15
14
13.5
20
12
18
30
10
22
35
10
27
40
6
34
45
6
41
50
6
52
70
4
62
80
4
80
125
2
100
150
1/0
125
175
2/0
144
200
3/0
208
400
2*1/0
250
400
2*2/0
Instruction Leaflet IL040016EN
Effective January 2022
Terminal connection
size (AWG)
Ground
Line and motor
Ground
14
26–10
18–10
12
26–10
18–10
10
26–10
18–10
10
20–6
12–6
10
20–6
12–6
8
20–6
12–6
8
6–2
14–4
8
6–2
14–4
6
6–2
14–4
6
6–1/0
10–1/0
6
6–1/0
10–1/0
4
6–1/0
10–1/0
4
1/0–350 kcmil
8–250 kcmil
4
1/0–350 kcmil
8–250 kcmil
4
1/0–350 kcmil
8–250 kcmil
3
2*(1/0–300 kcmil)
3–300 kcmil
3
2*(1/0–300 kcmil)
3–300 kcmil