PROBLEM
ALARM SIGNAL
Acquisition proce-
dure does not com-
plete correctly.
Barrier does not
perform desired
manoeuvre.
The barrier opens/
closes for a short
distance and then
stops.
The remote control
has limited range
and does not work
with the automa-
tion moving.
is not working.
Barrier open indi-
cator lamp does
not work.
N.B.
The next time a command is received, the alarm reappears on the display if the problem has not been resolved.
94
POSSIBLE CAUSE
Motor calibration failed.
TEST button pressed acciden-
tally.
Safety devices in alarm state.
Excessive voltage drop.
Incorrect setting of parameter
.
Incorrect setting of parameter
.
Incorrect values for installation
type.
Incorrect spring setting.
Battery operation management
(par.
different than
) not
detected.
Radio signals are impeded by
metal structures and reinforced
concrete walls.
Flat batteries.
light wires disconnected.
Bulb blown or wires discon-
nected.
CORRECTIVE ACTION
Repeat acquisition procedure.
If the problem persists, check the cable connecting
encoder 1 to the motor.
Check that the motor turns without impediment.
Contact technical support in case of any problems.
Repeat acquisition procedure.
Check connections of safety devices.
Repeat acquisition procedure; check mains voltage.
Select the correct installation position with param-
eter
. Repeat acquisition procedure.
Check type of boom and set parameter
Repeat acquisition procedure.
Set values of parameters
,
for installation type.
See the barrier instructions for spring balancing.
Change the value of the parameter
Install the antenna.
Replace the radio control batteries.
Check LED circuit and/or connector wires.
Check the bulb and/or wires.
correctly.
,
and
correctly
.