10 EN – USA Quick installation guide
9. Measure that the installation is de-energized.
Use a multimeter with an impedance of at least 1 Mohm.
Make sure that the voltage between the drive module input power terminals
(L1/U1, L2/V1, L3/W1) and the grounding (PE) busbar is close to 0 V.
Make sure that the voltage between the drive module UDC+ and UDC- terminals
and the grounding (PE) busbar is close to 0 V.
10. Install temporary grounding as required by the local regulations.
11. Ask for a permit to work from the person in control of the electrical installation work.
USA
Select the power cables
Size the power cables according to local regulations to carry the nominal current given on
DA
the type designation label of your drive.
Ensure the cooling and fuses (UL)
DE
See the table below for the losses and cooling air flow through the drive. The allowed
operating temperature range of the drive without derating is -15 to +40 °C.
ES
Drive type
FI
ACS580-505A-4
ACS580-585A-4
ACS580-650A-4
FR
ACS580-725A-4
ACS580-820A-4
ACS580-880A-4
IT
For more information, see the hardware manual 3AXD50000048677 (English).
NL
Protect the drive and input power cables
See the table above for the UL class fuses for branch circuit protection per NEC. Check
PL
that the operating time of the fuse is below 0.1 seconds. Obey local regulations.
Install the drive module into a cabinet
PT
See figure
B
on page 95:
Install the punched section to the back of the cabinet frame.
RU
Remove the pedestal guide plate from the bottom of the drive module.
Install the support rails and pedestal guide plate to the cabinet bottom frame.
SV
Install the telescopic insertion ramp to the pedestal guide plate.
For option +B051: See figure
TR
Remove the sheeting from the clear plastic shrouds from both sides.
ZH
Air flow
Heat dissipation
3
ft
/min
W
707
5602
707
6409
707
8122
707
8764
707
9862
848
10578
C
on page 95:
UL class
Fuse
Type
T
JJS-600
L
A4BY800
L
A4BY800
L
A4BY800
L
A4BY900
L
A4BY1000