14 EN – USA Quick installation guide
Default I/O connections
The default I/O connections of the ABB Standard macro are shown below.
1...10 kohm
USA
max.
500 ohm
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V DC).
ZH
Terminal sizes: 0.14...2.5 mm
Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)
XI
Reference voltage and analog inputs and outputs
1
SCR
2
AI1
3
AGND
4
+10V
5
AI2
6
AGND
7
AO1
8
AO2
9
AGND
X2 & X3
Aux. voltage output and programmable digital inputs
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
X6, X7, X8 Relay outputs
19
RO1C
20
RO1A
21
RO1B
22
RO2C
23
RO2A
24
RO2B
25
RO3C
26
RO3A
27
RO3B
X5
EIA-485 Modbus RTU
29
B+
30
A-
31
DGND
S4
TERM
S5
BIAS
X4
Safe torque off
34
OUT1
35
OUT2
36
SGND
37
IN1
38
IN2
X10
24 V AC/DC
40
24 V AC/DC+ in
41
24 V AC/DC- in
2
(all terminals)
Signal cable shield (screen)
Output frequency reference: 0...10 V
Analog input circuit common
Reference voltage 10 V DC
Not configured
Analog input circuit common
Output frequency: 0...20 mA
Motor current: 0...20 mA
Analog output circuit common
Aux. voltage output +24 V DC, max. 250 mA
Auxiliary voltage output common
Digital input common for all
Stop (0) / Start (1)
Forward (0) / Reverse (1)
Constant frequency selection
Constant frequency selection
Ramp set 1 (0) / Ramp set 2 (1)
Not configured
Ready run
250 V AC / 30 V DC
2 A
Running
250 V AC / 30 V DC
2 A
Fault (-1)
250 V AC / 30 V DC
2 A
Embedded Modbus RTU (EIA-485).
Serial data link termination switch
Serial data link bias resistors switch
Safe torque off. Factory connection. Both
circuits must be closed for the drive to start.
See chapter Safe torque off function in
ACS580-04 hardware manual
(3AXD50000015497 [English]).
Ext. 24V AC/DC input to power up the control unit
when the main supply is disconnected.