7.2.3. SSC parameters

Parameter Name
Teach-In Select
Teach-In Result
Teach-in State
TP1 (Teach Point 1) of
SP1 (Set point 1)
TP2 (Teach Point 2) of
SP1 (Set point 1)
TP1 (Teach Point 1) of
SP2 (Set point 2)
TP2 (Teach Point 2) of
SP2 (Set point 2)
SSC1 Parameter
(Switching Signal Channel 1)
Set point 1 (SP1)
Set point 2 (SP2)
SSC1 Configuration
(Switching Signal Channel 1)
Switching Logic
Mode
Hysteresis
SSC2 Parameter
(Switching Signal Channel 2)
Set point 1 (SP1)
Set point 2 (SP2)
SSC2 Configuration
(Switching Signal Channel 2)
Switching Logic
Mode
Hysteresis
38
Rev.00 - 06.2021 | MAN PD30CTP/R IO-Link EN | © 2021 | CARLO GAVAZZI Industr6
Index Dec
Access
(Hex)
58 (0x3A)
RW
59 (0x3B)
-
1 (0x01)
RO
2 (0x02)
RO
3 (0x03)
RO
4 (0x04)
RO
5 (0x05)
RO
60 (0x3C)
-
1 (0x01)
R/W
2 (0x02)
R/W
61 (0x3D)
-
1 (0x01)
R/W
2 (0x02)
R/W
3 (0x03)
R/W
62 (0x3E)
-
1 (0x01)
R/W
2 (0x02)
R/W
63 (0x3F)
-
1 (0x01)
R/W
2 (0x02)
R/W
3 (0x03)
R/W
Default value
0 = No Channel Selected
1 = SSC1
1 = SSC1 (Switching Signal Channel 1)
2 = SSC2 (Switching Signal Channel 2)
-
0 = Idle
4 = Wait for command
0 = Not OK
0 = Not OK
0 = Not OK
0 = Not OK
-
1 500 ... 0 (TRR/TPR)
100
1 500 (TRR/TPR)
1 500 ... 0 (TRR/TPR)
600 (TPS)
-
0 = High active
1 = Single Point
25%
-
1 500 ... 0 (TRR/TPR)
100
1 500 (TRR/TPR)
1 500 ... 0 (TRR/TPR)
600 (TPS)
-
0 = High active
0 = Deactivated
25%
Data range
Data Type
UIntegerT
-
-
0 = Idle
1 =Success
RecordT
5 = Busy
7 = Error
0 = Not OK
RecordT
1 = OK
0 = Not OK
RecordT
1 = OK
0 = Not OK
RecordT
1 = OK
0 = Not OK
RecordT
1 = OK
-
-
IntegerT
600 ... 0 (TPS)
IntegerT
600 ... 0 (TPS)
-
-
0 = High active
UIntegerT
1 = Low active
0 = Deactivated
1 = Single Point
UIntegerT
2 = Window
3 = Two Point
5 ... 99%
UIntegerT
-
-
IntegerT
600 ... 0 (TPS)
IntegerT
600 ... 0 (TPS)
-
-
0 = High active
UIntegerT
1 = Low active
0 = Deactivated
1 = Single Point
UIntegerT
2 = Window
3 = Two Point
5 ... 99%
UIntegerT
Length
8 bit
-
8 bit
8 bit
8 bit
8 bit
8 bit
-
16 bit
16 bit
-
8 bit
8 bit
16 bit
-
16 bit
16 bit
-
8 bit
8 bit
16 bit

Publicidad