CORRELATION BETWEEN GAS PRESSURE AND BURNER OUTPUT

To obtain the maximum output, it is necessary to have 4.5 mbar measured on the pipe coupling,
with the combustion chamber at 0 mbar and gas G20 - Pci = 10 kWh/Nm
6
5
4
3
2
1
0
10
D5037
10,000

GAS FEEDING LINE

1
2
3
1
– Gas arrival pipe
2
– Manual gate
(supplied by the installer)
3
– Gas pressure gauge
4
– Filter
5
– Gas pressure switch
6
– Safety valve
7
– Pressure governor
GAS TRAIN ACCORDING TO EN 676
MULTIBLOC
CODICE
MBC 65 DLE
3970569
The gas train is supplied separately; for its adjustment, see the enclosed instructions .
3302
15
20
15,000
20,000
M1
4
5
6
7
(supplied by the installer)
CONNECTIONS
TRAIN
Rp 1/2
25
30
25,000
Output
8
M2
8
– Adjustment valve
M1 – Gas-supply pressure test point
M2 – Pressure coupling test point
BURNER