Installation Instructions - JUNO FIREWALL IC1ALEDFW Instrucciones De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

JUNO FIREWALL™ FIRE RATED IC1ALEDFW
NEW CONSTRUCTION RECESSED HOUSINGS
ELECTRICAL CONNECTION
INSTRUCTIONS
Knock-
out
Quick
Connector
0-10V Dimming Wires
(-MVOLT models only)
Figure 6
Step 1. Provide electrical service according to
national and/or local electrical codes to the junction
box located on the fixture plaster frame. Supply
wire insulation must be rated for at least 90°C.
Step 2. Remove junction box cover. Remove the
appropriate knockout to accommodate the type of
electrical supply being utilized (Fig. 6).
Metal Conduit. Remove appropriate round knock-
out(s) and connect conduit to junction box with
proper connectors (not supplied).
12/2 or 14/2 Non-Metallic Sheathed Cable
(Type NM-B). Remove appropriate D-shaped cable
knockout(s). Insert the NM-B cable through the
cable trap and make a 90˚L-shaped bend in cable
as shown (Fig. 7).
12/3 or 14/3 Cable (Type NM-B). Remove the
appropriate round knockout and connect cable to
junction box with proper electrical connectors (not
supplied).
Step 3. Strip supply wires 3/8" and insert each
supply wire into appropriate quick connector.
Connect black fixture wire to hot, white fixture wire
to neutral and green fixture wire to ground (Fig. 6).
Connect violet (+) and gray (-) dimmer wires
if utilizing 0-10V dimmer.
Step 4. Place all wiring and connectors back in
wiring box and replace cover.
NM-B Cable
NM-B Cable
Knockout
(D-Shaped)
NM-B Cable
Trap
(4 Places)
12/2 or 14/2 NM-B Installation
Figure 7
WARRANTY
5-year limited warranty. Complete warranty terms located at
Technical Services Phone 1-800-705-SERV (7378)
One Lithonia Way • Conyers GA 30010 • Phone 1-800-705-SERV (7378) • Visit us at www.acuitybrands.com/juno-recessed
©2020 Acuity Brands Lighting, Inc

INSTALLATION INSTRUCTIONS

FIXTURE DIMMING
Multi-Volt LED 4" Downlights:
Universal input voltage (120VAC thru 277VAC)
housings. Dimmable with the use of most 0-10V wall
box dimmers.
120VAC LED 4" Downlights:
120VAC input housings. Dimmable with the use of
most incandescent, magnetic low voltage or electronic
low voltage* wall box dimmers.
Consult Juno Product Services or website for compatibility.
*Electronic low voltage dimmers require a neutral wire
connection in the wall box.
TRIM INSTALLATION
After ceiling is finished and painted, remove and
discard paint shield from fixture. Electronically connect
the trim to the wiring from the housing using the clear
connectors. Orient trim as desired for proper aiming.
Install trim into housing utilizing the trim push-in springs
(Fig. 8).
Trim Push-In
Springs
Figure 8
DRIVER REPLACEMENT
Driver replacement must be performed by
a qualified electrician. Before servicing, disconnect
or switch off electrical supply to fixture. Failure to do
so can result in electrical shock and/or injury.
Step 1. Remove trim from fixture by depressing lock
tab on electrical connector.
Step 2. Pull down inner housing to remove from
fixture. Disconnect red and black wires connecting
driver to inner housing and set aside (Fig. 9).
Step 3. Now access the fixtures wiring by carefully
pulling it through the opening. Once exposed you
can proceed with disconnecting the AC leads that
provide power to the driver and any applicable
dimming wires.
Step 4. Lift fire barrier flap on the side with the red
and black wires protruding (red and black wires
indicate driver location). The bottom of the flap will
have a half moon finger slot for easy lifting (Fig. 10).
Before lifting the flap, make sure the wires are
pushed out of the wire slots provided in the flap to
prevent tearing the fire barrier (Fig. 11). This will
allow access to the LED driver.
Step 5. Remove wing nut from driver plate to remove
driver plate from fixture (Fig.12). Pull driver plate out
while slightly lifting to release lower mounting feet.
Once free pull plate towards fixture opening and
rotate plate 90° so it will fit through fixture opening.
Driver plate rubbing against fire barrier is acceptable.
Step 6. Re-assemble fixture by completing steps 1
thru 5 in reverse order.
Inner
Figure 9
Housing
www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
Rev 06/20
P4748
HALF MOON
FINGER SLOT
JUNCTION BOX ACCESS
Step 1. Remove trim from fixture by depressing
lock tab on electrical connector.
Step 2. Pull down inner housing to remove from
fixture. Disconnect red and black wires connecting
driver to inner housing and set aside (Fig. 9).
Step 3. Now access the fixtures wiring by carefully
pulling it through the opening. Once exposed you
can proceed with disconnecting the AC leads that
provide power to the driver and any applicable
dimming wires.
Step 4. Lift fire barrier flap on the side with the red
Clear Electrical
and black wires protruding (red and black wires
Connectors
indicate driver location). The bottom of the flap will
have a half moon finger slot for easy lifting (Fig.
10). Before lifting the flap, make sure the wires are
pushed out of the wire slots provided in the flap to
prevent tearing the fire barrier (Fig. 11). This will
allow access to the LED driver.
Step 5 Open junction box door inside of fixture by
lifting black spring retention clip. Once junction box
door is released pull door out while slightly lifting to
release lower mounting feet. Once free pull plate
towards fixture opening and rotate plate 90° so it
will fit through fixture opening. Junction box door
rubbing against fire barrier is acceptable.
Step 6. Re-assemble fixture by completing steps
1 thru 5 in reverse order.
WING NUT
Figure 10
Junction
LED
Box
Driver
Figure 1 1
Figure 12
2 of 2