Operating and warning signals
Testing the radio circuit: After installation,
the radio connection must be tested for all
sensors!
Press the Test button for less than 5 seconds.
The networked sensors respond within a
max. 15 seconds with 2-3 short horn signals
at an interval of 2.5 seconds. The test alarm
is reset 2 minutes after the setting of the
sensor in question. Carry out the test on each
sensor in turn. If one of the sensors does not
respond. switch on the repeater function in
one of the intermediate sensors and repeat
the test.
Alarm: If an alarm is triggered, the horn of
the sensor in question will sound in intervalls
of 0.5 seconds. Within a max. of 15 seconds
the horn of the other networked sensors will
sound in intervals of 0.5 seconds. The sensor