Thermal Disinfection -Automatic - Franke AT3O0044 Instrucciones De Montaje Y Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

14.7 If the hot water temperature is > 70°C, the fitting should be flushed for at least 3
minutes. Trigger the fitting several times for this purpose.
The thermal disinfection process must be recorded (room, tapping point, date, time,
temperature, duration).
14.8 Turn the temperature selector (a) clockwise until it engages.
Caution!
The temperature selector (a) may not be turned beyond the stop in an anti-
clockwise direction.
14.9 Test the limit stop.
14.10 Trigger the fitting to drain the remaining hot water.
14.11 Measure the water temperature. The maximum water temperature may not exceed
40°C (see
Chapter
Once thermal disinfection has been completed, the scald protector does not need to
be reset.

15. Thermal disinfection -automatic-

Caution!
The directions in the Thermal Disinfection Planning Aid (01805618) must be
adhered to.
Required accessories
ECC2 function controller (60 W)
with Ethernet connection . . . . . 2000108123
Bypass solenoid valve cartridge . . 2000100431
10
16.).

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

At3o00467612982218002761298221824820300197352030019830

Tabla de contenido