5 - CONTROL PANEL
5.1 - DISPLAY
When power is on, the control unit checks that display correctly
operates by switching on all segments for 1.5 sec.
Pr I.0
Firmware version, e.g.
1.5 sec.
Panel will be viewed upon completion of this test.
CLOSED CONTACT
START
PEDESTRIAN
START
STOP
PHOTOCELL 1
PHOTOCELL 2
SAFETY RIBBON 1
PLEASE NOTE: if the panel is off, the control unit should be
in ENERGY SAVING mode; press the OK key to turn it on.
The control panel represents the physical status of the terminal
board contacts and of the program mode keys: if the upper
vertical segment is on, the contact is closed; if the lower vertical
segment is on, the contact is open (the above picture shows an
instance where the inputs PHOTO1, PHOTO2, EDGE1, EDGE2 and
STOP have all been correctly connected).
NOTE: if you are using an ADI module, other segments may
appear on the display, see the paragraph dedicated to the
"ADI INTERFACE"
Points being among display digits show the status of
programming push-buttons: as soon as a push-button is pressed,
its relevant point turns on.
The arrows on the left of the display show the state of the start
inputs. The arrows light when the related input is closed.
The arrows on the display right side show the gate status:
•
The highest arrow turns on when the gate is into its opening
phase. If it blinks, it means that the opening has been caused
by a safety device (border or obstacle detector).
•
The central arrow shows that the gate is on pause. If it blinks,
it means that the time countdown for the automatic closing
has been activated.
•
The lowest arrow blinks when the gate is into its closing
phase. If it blinks, it means that the closing has been caused
by a safety device (border or obstacle detector).
8.8.8.8
, will be viewed in the following
OPENED CONTACT
OPENING IN PROGRESS
PAUSE (GATE OPENED)
CLOSING IN PROGRESS
LIMIT SWITCH (SX)
LIMIT SWITCH (DX)
SAFETY RIBBON 2
OK
5.2 - USE OF THE KEYS FOR
PROGRAMMING
The control unit functions and times are programmed by means
of a special configuration menu, which can be accessed and
explored by using the 3 keys,
.
the control unit display.
PLEASE NOTE: Outside the configuration menu, pressing
h
the
key activates the START command, pressing the
activates the PEDESTRIAN START command.
The main programming menus of the control unit are shown in
the next pages.
To go through the menus use the three keys
according to the following chart:
5.3 - LANGUAGE SELECTION
The pre-set language is ITALIAN (
alternative language (ENGLISH).
To select another language, proceed as follows:
1.
Power the unit
2.
The display shows the firmware version of the micro-
controller and the language:
3.
While the display shows
shows the alternative language (E.g.
4.
Release the OK button: the new language has been set.
- 40 -
h
i
,
and OK, located on the side of
h
Press and release the push-button OK
Keep pressed the push-button OK for 2 seconds
Release the push-button OK
Press and release the push-button
Press and release the push-button
itA
) but you can select an
itA
itA
hold the OK button: the display
EnG
i
key
i
,
and OK
h
i
)