Energy saving function
In ON mode, operating conditions permitting, the dryer reduces
energy consumption by temporarily switching off the refrigera-
tion compressor; the ENERGY SAVING LED (3) comes on (see
Control Panel).
Scheduled maintenance
[
Y
When the DISPLAY
alternatively shows the Sr warn-
ing code and dew point, contact authorized assistance personnel
for carrying out scheduled maintenance indicated in par. 6.3 and
for resetting the warning code (see par. 5.4 in List of alarm/warn-
ings).
z
Press
to cancel the warning for 24 hours.
Condensate drain
There are three operation modes:
a) INTEGRATED --- draining controlled by the level sensor;
b) TIMED --- check that the automatic condensate drainage sys-
tem is working properly.
Use manual drainage to check that condensate is not retained
as this is symptomatic of poor drainage.
This check of the timed drain opening (parameter d1).
Settings depends upon the operating conditions of the dryer
and varies the amount of condensate to be removed.
For standard dryer operating conditions, see the following
table of recommended settings:
Model
PDRD265 ---1000
Parameter d1: time open in seconds for every 2 minutes of
operation.
c) EXTERNAL --- if there is an external drain
To change operation mode, use the parameter d3 (see par. 5.3 in
List of parameters)..
Y
Only set the EXTERNAL mode in absence of the solenoid
valve. Otherwise the relative coil could become damaged.
Alarm log
Contains the descriptions of the last alarms (max. 8).
é
Press
for 5 seconds: the keypad now operates in Alarm
MENU mode and the events can be scrolled with-
z
é
and
Every event is displayed with "ALx" (x=1--- 8).
AL1 = most recent event.
If there are no events "--- --- --- " appears.
To view the details of the event, press
ALx
1
Alarm code
2
Thousands of hours
3
Hours
4
Dew point
5
Evaporation temperature
6
Compressor discharge temperature
z
Scroll with
Parameter d1
5.3
Parameters
5
Accessing parameters
z
Press
and at the same time
in Parameters MENU mode and the parameters can be scrolled
z
with
and
(24VAC)
.
x
:
é
and
.
é
: the keypad now operates
é
.
.
List of parameters
A1
Sets the unit of measure for dew point in ˚C or ˚F.
Total hours of dryer operation = A3x1000+A2
A2/A3
(display only).
Like A2/A3 but for hours of refrigeration compressor opera-
A4/A5
tion.
Sets Hd Warning intervention temperature
A6
List of alarm/warnings).
A7
Inhibits remote OFF command.
b1
Sets the dryer address for serial communications.
b2
Sets the serial communication speed.
b3
Not available
b5
Refrigerant evaporation temperature.
b7
Not available
b8
Compressor discharge (delivery) temperature.
b9
Not available
Dryer model:
---
0 models PDRD250 ---1200
C5
---
1 models PDRD1400 ---3000
Sets compressor operation mode:
C7
---
CYC = CYCLING (energy saving enabled).
---
CON = CONTINUOUS (energy saving disabled).
Operating logic of the alarm/machine status relay.
0 = relay energised when dryer is running, de---energised if
in warning/alarm status.
C36
1 = relay de---energised when dryer is running, energised if
in warning/alarm status.
2 = relay de---energised when dryer is not running, energised
when running.
C37
% energy saving.
Sets the seconds of condensate drain opening (if set in
d1
TIMED mode).
d2
Like d1, but for seconds closed.
Sets condensate drain operation mode:
---
CAP = INTEGRATED
d3
---
tIM = TIMED
---
Con = EXTERNAL (24VAC)
4
PDRD265 ---1000