TABLE 3: Copper Cable Length in Feet (Service to Motor)
G-Series Motors: 1 Ph, 2-Wire Cable, 60 Hz. Wire Size
HP
Volt
14
0.5
115
110
0.5
230
438
0.75
230
365
1
230
304
1.5
230
219
G-Series Motors: 1 Ph, 3-Wire Cable, 60 Hz. Wire Size
HP
Volt
14
0.5
230
348
0.75
230
267
1
230
203
1.5
230
160
NOTE:
1. Maximum wire lengths shown maintain motor voltage at 95% of
service entrance voltage, running at maximum nameplate
amperes. If service entrance voltage will be at least motor name-
plate voltage under normal load conditions, 50% additional length
is permissable for all sizes.
2. Sizes given are for copper wire. For aluminum wire go two sizes
larger (i.e., if table lists #12 (3mm
aluminum wire.)
INSTALLATION WIRING INSTRUCTIONS
Single Phase, 3 Wire
Hazardous voltage. Can shock, burn, or kill.
Ground control box, all metal plumbing, and motor frame with copper
wire in compliance with Canadian Electrical Code or National Electrical
Code and local codes. Use ground wire at least as large as the wires
supplying power to motor.
At well head, connect ground wire to grounding terminal that meets
Canadian Electrical Code or National Electrical Code requirements that
apply. For more information, contact local code officials.
Permanently close all unused openings in this and other equipment.
Disconnect power before working on or around control box, pipes, cable,
pump, or motor.
NOTICE: Install control box vertically on wall with top side up.
3-Wire pumps have three power supply wires (Red/Black/Yellow) and
one ground wire (Green).
Attempting to operate 3 wire pump without a control box will burn out the
motor.
Installations must include circuit and component protection in compli-
ance with U.S. National Electrical Code or Canadian Electrical Code,
Part 1.
If main overload trips, look for:
1. Shorted Capacitor
2. Voltage Problems
3. Overload or locked pump.
NOTICE: Use only control box specified for your pump. Make sure
motor and control box match (Table 4). FAILURE TO DO SO WILL
VOID WARRANTY.
Table 4: Control Box Chart
HP
Voltage
1/2
230
3/4
230
1
230
1-1/2
230
For motors of 1-1/2 HP and above, use magnetic
starter to avoid damage to pressure switch. Consult factory for
wiring information.
Wire Size, AWG
12
10
8
6
174
278
440
685
697
1112
1761
2740
581
927
1468
2284
484
772
1223
1903
349
556
881
1370
Wire Size, AWG
12
10
8
6
553
883
1398
2175
425
678
1074
1671
323
515
815
1269
254
406
643
1000
) copper wire, use #10 (5mm
2
Control Box No.
SD-F303
SD-F304
SD-F305
SD-F306
4
3
2
1092
1373
1734
2184
4369
5492
6936
8738
3641
4577
5780
7281
3034
3814
4817
6068
2184
2746
3468
4369
4
3
2
3467
4359
5505
6935
2664
3349
4229
5328
2023
2543
3211
4045
1594
2004
2531
3189
Fig. 1A – 3 wire - 1/2 thru 1 HP quick disconnect box.
Follow color coding when connecting control box.
(Yellow to Y, Red to R, Black to B)
115V or
Ground
230V Line
Fused
disconnect
)
2
switch
L1 M1
L2
M2
Red
Yellow
Black
Well
casing
Single Phase, 2 Wire
2-Wire pumps have two power supply wires (Red/Black) and one
ground wire (Green). Control box is not required.
See Figure 1B for correct hook-up information for 230 Volt 2-Wire
motors only.
Fig. 1B – Single phase, 2 Wire Connections
To Line
Fused
Disconnect
Switch
3
1
0
00
2757
3479
11029
9191
11596
7659
9663
5515
6957
1
0
00
8753
6725
8485
5106
6442
4025
5078
Sub.
Motor
Control
L1L2R Y B
Pressure
switch
Ground
699 0993
Ground
L1
M1
L2
M2
Pressure
Switch
Black
Black
Ground
(Green)
Well
Casing
6109 1009

Publicidad

Tabla de contenido
loading

Tabla de contenido