Installer setup
Setup function
Shaded areas below apply only to
10
Stage 2 compressor
cycle rate (CPH)
12
Manual/Auto
changeover
13
Adaptive Intelligent
Recovery™
14
Temperature
display
15
Compressor
protection
16
Schedule format
27
Heat temperature
range stops
28
Cool temperature
range stops
Installer system test
press and hold the
buttons until the display changes.
System test
Shaded areas below apply only to
10
Heating system
20
Emergency heating
system
30
Cooling system
40
Fan system
CAUTION: Compressor protection is bypassed during testing. To prevent equipment
Settings & options (factory default in bold)
TH6320U/TH6220D
3
Recommended for most compressors
0
Manual changeover (Heat/Cool/Off)
1
Auto changeover (Heat/Cool/Auto/Off) **See page 8
2
Auto changeover only (Auto) **See page 8
1
On**See page 8
0
Off
0
Fahrenheit
1
Celsius
5
Five-minute compressor off time **See page 8
0
5/2 (programmable weekdays and weekends)
90
Max. heat temperature setting is 90° F (32° C)
[Other options: 40 °F to 89 °F (4.5 °
50
Min. cool temperature setting is 50° F (10° C)
[Other options: 51 °F to 99 °F (10.5 °
and
System status
TH6320U/TH6220D
0
Heat and fan turn off.
2
Stage 2 heat turns on
0
Heat and fan turn off
1
Heat and fan turn on
0
Compressor and fan turn off
1
Compressor and fan turn on
2
Stage 2 compressor turns on
0
Fan turns off
1
Fan turns on
7
FocusPRO
or as otherwise noted.
°C)]
Test number
10
Press
/
to turn system on/off.
Press NEXT to advance to next test.
or as otherwise noted.
TH6320U
only
TH6000 Series
®
System status
0
MCR29455
69-2695EFS— 01