Installer setup
Setup function
Shaded areas below apply only to
9
Stage 1 compressor
cycle rate (CPH)
10
Stage 2 compressor
cycle rate (CPH)
12
Manual/Auto
changeover
14
Temperature
display
15
Compressor
protection
26
Auxiliary heat control
27
Heat temperature
range stops
28
Cool temperature
range stops
Installer system test
To begin, press and hold the
n,
n,
p
press and hold
press and hold
buttons until the display changes
ons until the display chang
ns until the display chang
System test
stem test
Shaded areas below apply only to
haded areas below appl
10
10
10
Heating system
Heating system
yst
20
Emergency heating
system
30
Cooling system
40
Fan system
CAUTION: Compressor protection is bypassed during testing. To prevent equipment
!
damage, avoid cycling the compressor quickly
FocusPRO
Settings & options (factory default in bold)
TH5320U/TH5220D
3
Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
3
Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
0
Manual changeover (Heat/Cool/Off)
1
Auto changeover (Heat/Cool/Auto/Off)
2
Auto changeover only (Auto)
0
Fahrenheit
1
Celsius
5
Five-minute compressor off time
[Other options: 0, 1, 2, 3 or 4-minute off time]
0
Comfort **See page 8
1
Economy
90
Max. heat temperature setting is 90 °F (32 °C)
rature setting is 90 °F (32
ture setting is 90 °F
[Other options: 40 °F to 89 °F (4.5 °C to 31.5 °C)]
40 °F to 89 °F (4.5 °C to 31.5
o 89 °F (4.5 °C to 31
50
Min. cool temperature setting is 50 °F (10 °C)
temperature setting is 50
temperature setting is 50
[Other options: 51 °F to 99 °F (10.5 °C to 37 °C)]
ptions: 51 °F to 99 °F (10.5 °
ons: 51 °F to 99 °F (10.5 °
the
e
and
a
System status
TH5320U/TH5220D
0
Heat and fan turn off.
1
Stage 1 heat turns on. Fan turns on if Setup Function 1 is set to 1,
5, 9 or 10 OR Setup Function 3 is set to 1 **See page 6
2
Stage 2 heat turns on
3
Stage 3 heat turns on -
0
Heat and fan turn off
1
Heat and fan turn on
2
Stage 2 heat turns on (auxiliary heat) -
0
Compressor and fan turn off
1
Compressor and fan turn on
2
Stage 2 compressor turns on
0
Fan turns off
1
Fan turns on
TM
TH5110 / TH5220 / TH5320
or as otherwise noted.
me
me
minute off time]
inute off time
°F (10 °C)
F (10 °C)
°C)
C)
System status
T
T
Test number
10
Press
/
to turn system on/off.
Press NEXT to advance to next test.
Press DONE to terminate system test.
or as otherwise noted.
TH5320U
only
TH5220D
only
0