Monitor Operation
The Hyst(eresis) screen displays. This value, added to the alarm
level, tells the monitor at which level to deactivate the alarm
(e.g. Alarm level A is 25 ppm, minus a hysteresis level of -05,
gives a deactivation level of 20 ppm). Use the arrow keys to
increase or decrease the value and press enter. A confirmation
screen displays. Press enter to confirm.
The screen briefly displays a success message and returns to the main
menu option.
30
SetAlarm
Yes
E
Point Gas Monitor Technical Manual