Monitor Operation
Menu
Description
Options
Simulates events for testing purposes
TestMode
without affecting the sensor readings. Used
during installation.
Reserved for authorized Honeywell Analytics
Memory
technicans only.
Exits the programming menus and returns
Quit?
the device to normal operation mode.
Model Shared Menu Options
Password Menu
Access to the programming menus is password protected (password is
HA). The Password screen displays after pressing the enter key.
•
Press the arrow key (up or down) to change the first letter to H.
•
Press enter and use the arrow keys to change the
second letter to A.
Press enter to confirm the password and access the menus.
•
•
Use the arrow keys to scroll through the menu options.
•
In the event of an entry error, the monitor returns to normal display
mode. Restart the login process.
Network Menu
The Network menu contains several sub-menu options: Address,
BaudRate, BACnet ID, and Protocol. Use the arrow keys to scroll to the
desired option and press enter to select:
Address:
Use the arrow keys to increase or decrease the address value
(from 001 to 254 in Modbus or 1 to 127 in BACnet) and press
enter to confirm the desired address
BaudRate: Use the arrow keys to scroll through predefined baud rates
(4800, 9600, 19200, 38400, 57600, 76800) and press enter
to select.