Password Menu; Network Menu - Honeywell E3Point Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Monitor Operation
Menu
Description
Options
Simulates events for testing purposes
TestMode
without affecting the sensor readings. Used
during installation.
Reserved for authorized Honeywell Analytics
Memory
technicans only.
Exits the programming menus and returns
Quit?
the device to normal operation mode.
Model Shared Menu Options

Password Menu

Access to the programming menus is password protected (password is
HA). The Password screen displays after pressing the enter key.
Press the arrow key (up or down) to change the first letter to H.
Press enter and use the arrow keys to change the
second letter to A.
Press enter to confirm the password and access the menus.
Use the arrow keys to scroll through the menu options.
In the event of an entry error, the monitor returns to normal display
mode. Restart the login process.

Network Menu

The Network menu contains several sub-menu options: Address,
BaudRate, BACnet ID, and Protocol. Use the arrow keys to scroll to the
desired option and press enter to select:
Address:
Use the arrow keys to increase or decrease the address value
(from 001 to 254 in Modbus or 1 to 127 in BACnet) and press
enter to confirm the desired address
BaudRate: Use the arrow keys to scroll through predefined baud rates
(4800, 9600, 19200, 38400, 57600, 76800) and press enter
to select.
18
Password
AA
* Menu *
Network
E
Point Gas Monitor Technical Manual
3
Menu Type
Shared menu
Shared menu
Shared menu

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

1309a00381309a00591309a00511309a0061

Tabla de contenido