Annex A - Bacnet And Modbus Objects On E; Bacnet Configuration; Bacnet Objects Descriptions; Point Network - Honeywell E3Point Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Annex A - BACnet and Modbus Objects
The E
Point Network can be factory configured with optional
3
communication types: BACnet or Modbus. Each of these communication
protocols has its own specific objects.
Honeywell recommends that appropriate measures be taken to ensure
security since BACnet and Modbus are not inherently secure. The installer
takes all responsibility for protecting the controller from malicious network
traffic.

BACnet Configuration

The E3Point is an MSTP Master Device and supports Dynamic Device
Binding (WHOIS/IAM), which is part of BACnet protocols DM-DDB-B
and DM-DOB-B (see the
Statement

BACnet Objects Descriptions

Each measurement type has Analog Input (AI), Analog Value (AV), Binary
Output (BO) and Binary Value (BV) objects. The table below defines each
object and lists the default setting:
Type
Name
AI
Conc.
AV
Alr A
AV
Hyst A
AV
Alr B
AV
Hyst B
BV
Hi
Temp
Fault
BO
Relay
BO
Buzzer
E
Point Gas Monitor Technical Manual
3
Annex A - BACnet and Modbus Objects on E3Point Network
on E

Point Network

3
section for details).
The gas reading
The level at which Alarm A will be triggered
Alarm A hysteresis offset (Alr A + Hyst A = level at
which alarm is deactivated)
The level at which Alarm B is triggered
Alarm B hysteresis offset (Alr B + Hyst B = level at
which alarm is deactivated)
Temperature High Level limit
Actual buzzer status (on or off)
Actual relay status (on or off)
Protocol Implementation Conformance
Description
Read/
Write
R
R/W
R/W
R/W
R/W
R
R/W
R/W
39