Maintenance Table V (Hs, Hp) Series, Part 3 Of; Cilindros Más Accionados - GEA Grasso VHS Serie Manual De Instalación Y Mantenimiento

Compresores alternativos para refrigeración industrial
Tabla de contenido

Publicidad

3.4.3.3 Maintenance table V (HS, HP) Series, part 3 of 3

GEA Grasso Maintenance intervals, part 3 of 3
GEA GRASSO MAINTENANCE INTERVALS AND ACTIVITIES
Main system
Sub system
Outside
Structure
Fixation
Intake suction filter/screen
COMPRESSOR
HOUSING
Crankcase-oil heating
Oil return orifices HP LP
Safety relief valve(s)
Inside
Structure
BASE FRAME
Fixation
Vibration dampers
Temperature gauges
COMPRESSOR
sensors/switches/transmitters
PROTECTION /
SAFETY &
Pressure
CONTROL DEVICES
Controls
Coupling
DRIVE
V-Belts
E-MOTOR
INTERSTAGE
COOLER
3.4.3.4 Cilindros más accionados
P-NL-094_imm_VHS_Spanish~_13
26.07.2021
ESQUEMA DE MANTENIMIENTO Y SERVICIO
Mechanical part
Seals & gaskets Leaks
Connection/lines & working
Connection/lines
Cabinet, consoles / fixation
Alignment
Bolts tightening
Wear & alignment
Bearings Lubrication
Injection valve
MANTENIMIENTO
Flexible:
Depending on running
conditions and shown by
GMM or OMNI
- - - - - - - - - -
Fixed:
To be monitored by
Whatever
operator
comes first:
Flexible
Yearly or
interval:
every
VM 6.000 -
6.000 hr at
18.000 hr
1200 RPM
VL 7.500 -
5.000 hr at
18.000 hr
1500 RPM
Fixed
interval:
12.000 hr at
1200 RPM
- - - - -
10.000 hr at
1500 RPM
A
B
CLEAN
CLEAN
CLEAN
CHECK
CHECK
INSPECT
INSPECT
CLEAN
CLEAN
INSPECT
INSPECT
INSPECT
CHECK
CHECK
CHECK
CHECK
CHECK
CHECK
CHECK
CHECK
CHECK
CHECK
CHECK
CHECK
ACCORDING MANUFACTURER'S MANUAL
CHECK
CHECK
Flexible
interval:
VM 40.000 –
47.000 hr
VL 40.000 –
54.000 hr
Fixed
interval:
36.000 hr at
1200 RPM
- - - - -
30.000 hr at
1500 RPM
C
CLEAN
CLEAN
CHECK
INSPECT
CHECK
CLEAN
INSPECT
INSPECT
INSPECT
CHECK
CHECK
CHECK
CHECK
CHECK
CHECK
CHECK
51

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Grasso v 700hsGrasso v 1100hsGrasso v 1400hsGrasso v1800hs

Tabla de contenido