9.16 Code 181 (Signal fault, PTC input)

Alarm code 181 is shown on the display.
The alarm symbol on the display turns red and the pump stops.
Alarm code Signal fault, PTC input is displayed in Grundfos
GO Remote.
Cause
There is a signal fault in the PTC input.
Remedy
Make sure that the two PTC wires from the pump are
connected correctly to the terminals on the product.
Make sure that the third PTC wire is left unconnected, if
present.
Make sure that the PTC wires are undamaged.
Make sure that the PTC sensors within the pumps are
undamaged.
Perform a test by disconnecting the PTC wires from the
pump and shorting PTC1 terminal A and B and also PTC2
terminal A and B, and verify that the error is cleared.
Replace the product due to damaged PTC circuit. Contact
Grundfos.

9.17 Code 191 (High water level)

Alarm code 191 is shown on the display.
The alarm symbol on the display turns red, but the pump's
operating mode is unchanged.
Alarm code High water level is displayed in Grundfos GO
Remote.
Cause
The defined start level did not start the pump.
Remedy
Check and configure the sensor start level.
Cause
The pump is not big enough to remove the water.
Remedy
Contact Grundfos or an authorised service workshop.
Cause
The level sensor is defective and not reacting on level changes.
Remedy
Check the functionality of the level sensor.

9.18 Code 205 (Level switch inconsistency)

Alarm code 205 is shown on the display.
The alarm symbol on the display turns red and the pump
stops.
Alarm code Level switch inconsistency is displayed in
Grundfos GO Remote.
Cause
A float switch could be defective or stuck.
Remedy
Check the functionality of each float switch.

9.19 Code 225 (Communication error pump module)

Alarm code 225 is shown on the display.
The alarm symbol on the display turns red and the pump
stops.
Alarm code Communication fault, pump module is displayed
in Grundfos GO Remote.
The product is unable to communicate with the IO module.
Cause
The connection to GENIbus is missing.
Remedy
Check the GENIbus connection cable between CU 24X and
IO 242.
Cause
The pump module is defective.
Remedy
Contact Grundfos.

9.20 Code 226 (Communication error IO module)

Alarm code 226 is shown on the display.
The alarm symbol on the display turns red and the pump
stops.
Alarm code Communication fault, I/O module is displayed in
Grundfos GO Remote.
The product is unable to communicate with the IO module.
Cause
The connection to GENIbus is missing.
Remedy
Check the GENIbus connection cable between CU 24X and
IO 241.
Cause
The IO module is defective.
Remedy
Contact Grundfos.

9.21 Code 229 (Water on floor)

Warning code 229 is shown on the display if you press
the Up or Down button.
The warning symbol on the display turns yellow and the pump's
operating mode is unchanged.
Warning code Water on floor is displayed in Grundfos GO
Remote.
Cause
The sensor detects water on the floor.
Remedy
Check for water leakage.

10. Technical data

Supply voltage
24 VDC, - 10 %/+ 10 %.
Power supply is required to be class 2.
Check that the supply voltage corresponds to the values stated on
the nameplate.
Maximum power dissipation
Object
99347490
*
Excluding power to USB and CIM modules.
Maximum input power
Object
99347490
Enclosure class
IP54, 3R for CU 24X built into a panel of similar or higher enclosure
class.
GENIbus terminal
- 7 to + 12 VDC.
Nominal current condition: 4 mADC.
Short-circuit current condition: 328 mA.
Maximum power dissipation
*
3 W
Maximum input power