Novoferm tormatic TAD MS 400V Manual De Instrucciones Y De Montaje página 30

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 62
Spring balancing check
Once the door has been opened and closed completely, you can
check the spring balance in menu item 47. Keep the 
pressed for 5  seconds. The LED display now indicates the bal-
ance value of the door:
The display value should be between -1 and +2, otherwise you
must re-adjust the springs.
The remaining weight (F [kg]) of the spring balanced door can be
calculated as follows:
Motor 9.24/5.24
F [kg] = display value x 20 kg / U
Motor 9.20
F [kg] = display value x 16 kg / U
Motor 9.15
F [kg] = display value x 15 kg / U
U = number of revolutions for one door opening process
F = remaining weight in kg of the spring balanced door
The results are only to be considered as approximate
values. For an exact calculation, perform a force measurement
process.
If 6.65DU is used, the function will deviate.
NOTICE
For this, please take the "DU function" section
into consideration.
Opening force limit (menu item 48)
Danger of entanglement on the door leaf by
WARNING
persons standing or sitting on the door while
it is moving!
The force limitation must be set so as to prevent
persons from being able to stand or sit on the
door while it is moving.
Force limitation can only be utilized for doors
NOTICE
with spring balancing.
Environmental impacts like wind load and tem-
perature variations may lead to unintentional trig-
gering of the force limitation function.
Carry out the following settings for opening force limitation in
menu item 48 in compliance with the motor used:
Motor 9.24/5.24
Input value = U x weight / 20 kg
Motor 9.20
Input value = U x weight / 16 kg
Motor 9.15
Input value = U x weight / 15 kg
The results are only to be considered as approximate
values. For an exact calculation, perform a force measurement
process.
The opening cycles are compared to the previous travel process.
If the value set is exceeded, the door stops and F33 appears on
the LED display.
Afterwards, the door can only be closed in dead man
mode.
Eliminate the cause of the excess of force, then open and close
the door once.
Force measurement process (menu item 48)
Danger of entanglement by the moving door!
WARNING
Force monitoring does not replace the need for
safety measures against the danger of entangle-
ment!
Perform a force measurement process to exactly determine the
switch-off threshold for force monitoring:
1.
Select the value 99 in menu item 48.
ð
The control starts a force measurement process.
28 - EN
2.
Install a test weight on the door (approx. 20 kg are recom-
mended) and completely open and close the door.
3.
The value measured appears on the LED display and is ac-
 button
cepted as switch-off value. The switch-off value can be
changed (double value equals double force).
4.
Remove the test weight and completely open and close the
door again.
Functional force monitoring check
Upon completion of the force measurement process, carry out a
functional check of the force monitoring function. Install the test
weight on the door again for this purpose. The drive must switch
off!
NOTICE
Duty cycle (menu item 49)
The duty cycle set prevents the drive motor from being over-
heated and avoids damage.
NOTICE
Menu 5 Various settings
External command transmitter (menu item 51)
If external command transmitters are used, the respective setting
must be adjusted in menu item  51 according to the connection
and type of command transmitter. Set the value as follows:
If you use a command transmitter on the input J1.3 for pulse gen-
eration CLOSED and on the input  J1.4 for pulse genera-
tion OPEN, set the value to 1.
If you use a command transmitter with OPEN-STOP-CLOSE
switching sequence on J1.3 (1/2 door opening) or on J1.4 (com-
plete door opening), set the value to 0.
CAUTION
Smoke and heat extraction function (menu item 55)
Select the corresponding door position in menu item 55. Connect
the fire alarm system to J7 and select the value  7 in menu
item 50.
Selection of the control type (menu item 59)
In menu item  59, various control variants are selected. For cor-
responding settings please refer to the supplementary sheets.
NOTICE
TAD MS 400V / 230V
Force monitoring has not tripped during the
functional check
If the force monitoring function has not tripped,
the settings in menu item 48 must be checked.
The force measurement process must be re-
peated.
Motor 5.24 with a plastic gearbox
When motor 5.24 with a plastic gearbox is used,
the duty cycle must be set to the value 1 (3~) or
2 (WS, 1~).
Crush hazard and risk of being struck by the
closing door
Persons can be struck when the door is closed
or collide with the door.
The door must be visible from the place of
operation.
Make sure that the settings are correct
Incorrect settings can cause damage or malfunc-
tion of the control.

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Tad ms 230vHad ms 400vHad ms 230v

Tabla de contenido