Installation
Caution!
Installation must be made by qualified personnel and conform to ANSI/NFPA 70 (the National
!
Electrical Code
and all applicable local codes. Bosch Security Systems, Inc. accepts no liability for any
damages or losses caused by incorrect or improper installation.
Notice!
To meet the Mains Supply Voltage Dips and Short Interruptions requirements per EN 50130-4
Alarm Standard, ancillary equipment (for example, UPS) is necessary. The UPS must have a
Transfer time between 2-6 ms and Backup Runtime of greater than 5 seconds for the power
level as specified on the product data sheet.
Notice!
To maintain the IP (protection) rating of the enclosure, install only listed or recognized glands
with the same environmental rating as the enclosure according to the installation instructions
of the gland.
Note: All item numbers referenced in the following steps refer to the MIC-ALM-WAS-24 Layout.
To install the MIC-ALM-WAS-24, follow these steps:
1. Select a secure installation location for the device. Ideally, this is a location where the
device cannot be interfered with intentionally or accidentally and that will ensure that
environmental conditions are within the rated specifications.
To provide maximum protection against EMC interference, install the device inside an
environmentally suitable equipment cabinet that has a good connection to earth ground.
2. Remove the lid.
3. Mount the device to a stable surface, if desired.
Bosch Security Systems
(NEC)), Canadian Electrical Code, Part I (also called CE Code or CSA C22.1),
®
Loosen the four (4) M4 screws and remove the lid of the enclosure (item 1).
Locate the four (4) mounting holes (item 2).
If applicable, drill four (4) holes in the mounting surface, using the figure below as
reference.
Secure the enclosure to the mounting surface using M4 (#8) screws and washers (not
supplied).