Parker Hyperchill-Plus ICEP007 Manual De Uso página 55

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

7.3 Techincal data
MODBUS
unit adress
BaudRate
9600
Protocol Parity
Address Display label
App type Default
8964
Set
INT
8965
dIF1
INT
8966
dIF2
INT
8969
OFFC
INT
8970
ONC
INT
8973
LiS
INT
8974
HA1
INT
8975
LA1
INT
8976
db1
INT
8977
HA2
INT
8978
LA2
INT
8979
dI2
INT
8980
HA3
INT
8981
LA3
INT
8982
SEA
INT
8983
dIA
INT
8984
ArA
INT
8985
DtHA
INT
8986
SRQH
INT
8987
drq
INT
8988
SrC
INT
8989
drC
INT
8990
SRQL
INT
8995
PStA
INT
8996
SUP
BOOL
16385
rE
USINT
16387
SUP
BOOL
16384
C-F
BOOL
16386
rAL
USINT
16388
Ud4E
BOOL
16390
ASt
BOOL
16391
r0n
UINT
16465
CPT
BOOL
16445
Erd
BOOL
8999
Dma
INT
8961
dMin
INT
16423
dAS
USINT
16431
tH1
INT
16472
tH1L
INT
16409
CHA1
BOOL
16414
CHA2
BOOL
16411
CLA1
BOOL
16419
rLa
USINT
16420
tLa
USINT
16432
AbPd
BOOL
16433
dPOn
USINT
1
EVEN
NONE
1
ODD
Min
Max
13(55,4)
LIS
65(149)
4(7,2)
0,3(0,5)
10(18)
0,3(0,5)
0,3(0,5)
10(18)
2(3,6)
ONC
10(18)
1(1,8)
0(0)
OFFC
5(41)
LA2
65(149)
60(140)
-40(-40)
65(149)
-40(-40)
-40(-40)
65(149)
1(1,8)
1(1,8)
10(18)
60(140)
-40(-40)
65(149)
2,5(36,5)
-40(-40)
65(149)
4(7,2)
1(1,8)
10(18)
60(140)
-40(-40)
65(149)
-30(-22)
-30(-22)
65(149)
19(66,2)
LIS
65(149)
1(1,8)
1(1,8)
10(18)
5(41)
-30(-22)
65(149)
5(9)
0(0)
30(54)
30(86)
-10(14)
55(131)
19(34,2)
0(0)
30(54)
15(59)
-30(-22)
50(122)
2(36)
0(0)
10(18)
5(41)
-10(14)
30(86)
0
0
1
FALSE
FALSE
TRUE
0
0
2
FALSE(0)
FALSE(0)
TRUE(1)
FALSE(0)
FALSE(0)
TRUE(1)
0
0
2
FALSE(0)
FALSE(0)
TRUE(1)
TRUE(1)
FALSE(0)
TRUE(1)
6
0
300
FALSE(0)
FALSE(0)
TRUE(1)
FALSE(0)
FALSE(0)
TRUE(1)
25(77)
0(32)
37(98,6)
15(59)
-20(-40)
37(98,6)
5
0
10
0
0
9999
0
0
9999
TRUE(1)
FALSE(0)
TRUE(1)
TRUE(1)
FALSE(0)
TRUE(1)
FALSE(0)
FALSE(0)
TRUE(1)
5
0
15
60
5
60
TRUE(1)
FALSE(0)
TRUE(1)
15
dLE
60
ICEP007-024 (60Hz)
Not configurable
Stop Bit
Data Bit
Address with offset 40000 (es: 8964+40000=48964)
Unit
Read Only
Note
°C/(°F)
FALSE
Set point
°C/(°F)
FALSE
Differential 1 for thermostating
°C/(°F)
FALSE
Differential 2 for thermostating
°C/(°F)
FALSE
Differential for compressor OFF
°C/(°F)
FALSE
Dirrerential for compressor ON
°C/(°F)
FALSE
Set point lower limit
°C/(°F)
FALSE
B1 High terperature alarm
°C/(°F)
FALSE
B1 Low temperature alarm
°C/(°F)
FALSE
B1 Low level temperature alarm retrigger
°C/(°F)
FALSE
B2 High temperature alarm
°C/(°F)
FALSE
B2 Low temperature alarm
°C/(°F)
FALSE
B2 Alarm differential
°C/(°F)
FALSE
B3High temperature alarm
°C/(°F)
FALSE
B3 Low temperature alarm
°C/(°F)
FALSE
Set point (B1) antifreeze
°C/(°F)
FALSE
Thermostating differential (B1)
°C/(°F)
FALSE
Set point activation (B3)
°C/(°F)
FALSE
Differential for dipendent water exit regulation
°C/(°F)
FALSE
SetH point for control panel heater
°C/(°F)
FALSE
Differential control panel heater
°C/(°F)
FALSE
Setpoint Carter Heater
°C/(°F)
FALSE
Differential value for carter heater
°C/(°F)
FALSE
SetL point for control panel resistor
TRUE
Status ON/OFF dryer
FALSE
Supervisor ON OFF request (to change the state machine - change True from "0" to "1")
FALSE
Remote ON/OFF enable
FALSE
ON/OFF enable from supervison
FALSE
Unit of measure (FALSE=°C, TRUE=°F)
FALSE
Alarm relè management
FALSE
Enable antifreeze resistor 0=disabled
FALSE
Autostart enable 0=NO 1=YES
sec
FALSE
Main power supply return
FALSE
CPT control 1=Enable
FALSE
Enable managing water with Ambient temperature
°C/(°F)
FALSE
Max value to stop compressor in ERD
°C/(°F)
FALSE
Min value to run compressor in ERD
Minutes
FALSE
Minimun time between two switch ON of the same compressor (minutes)
KHours
FALSE
Compressor 1 working hours warning threshold (x1000)
Hours
FALSE
Compressor 1 working hours warning threshold
FALSE
HA1 alarm management
FALSE
HA2 alarm management 0=Warning; 1=Alarm; 2=System
FALSE
LA1 alarm management
FALSE
Max number of Events LA2 Alarm
Minutes
FALSE
Interval Time LA2 Alarm
FALSE
Enable delay switching on pump
Sec
FALSE
Delay switching ON pump (sec) at power on
10

Publicidad

Tabla de contenido
loading

Tabla de contenido