6.7 OPERATION PARAMETER

The OPERATION PARAMETER function is for installer or service
engineer to review the operation parameter.
You can check the water temperature, water flow, pressure
and other parameters by using "OPERATION PARAMETER".
1. POWER CONSUM is for reference only, not used to
judge the actual power consumption. Keep pressing ''▼"
and ''►''at the same time for 8 seconds, then POWER
CONSUM can be reset to zero.
2. HEAT PUMP CAPACITY is for reference only, not used
to judge the actual capacity of the unit.
3. If some parameter is not activated in the system, the
parameter will be displayed "--".
4. The accuracy of sensor is ±1℃.
5. The flow rate is calculated according to the pump
running parameters, the deviation is different at
different flow rates, the deviation is about 15%.
6. The flow rate is displayed "0" when the voltage is less
than 198V.
INFORMATION
i
54
V.1