Connecting
WARNING
Hazardous voltages from the mains power input or heat
emitter lines
may cause death, serious injury or damage to property
Dangerous voltages may be present on incoming lines
from the supply and to heat emitters.
Before work starts on connecting the HCS3200 heating
controller, the incoming supply and heat emitter lines must
be disconnected and secured against being switched on
again.
Location of connection elements: See Figure 4
Connection diagram: See Figure 7
Recommended connector accessories with order number:
See Figure 6
You can procure further accessories for X1 and X2 via the
Harting (http://www.harting.com/en/home/).
You can procure accessories for X3 and X4 via Siemens
Industry Mall (www.siemens.com/siplus/mall).
X1 Mains connection / protective conductor connection
X2 Emitter connection
X3 PROFIBUS DP / 24 V DC supply voltage
X4 PROFIBUS DP / 24 V DC supply voltage
WARNING
Electric shock hazard / fire hazard
Danger to life or danger of serious injury
Voltages to ground of 230 V AC may be present at X2.
•
The connection cables must have double or reinforced
insulation.
The protective conductor for the device is connected to
•
plug connector X1.
The protective conductor must be attached to the
connector in accordance with the instructions of the
manufacturer.
Technical specifications
Connection data
Rated voltage
Switching capacity per
phase
Number of output channels
4
400 V AC (±10 %), 50/60
Hz, TN system
63 A
9
Maximum switching
capacity per output channel
Fuse for each output
channel
Total switching capacity of
the device
Overvoltage category
Controller power supply
Voltage
Current consumption
Ambient conditions
Note: For indoor use only.
Ambient temperature in
operation
Ambient temperature during
storage and transport
Relative humidity in
operation
Degree of protection
Maximum height above sea
level
Mechanical specifications
Weight
Dimensions (W x H x D)
Approvals / standards
CE
UR
Technical Assistance
Telephone: +49 (0) 911-895-5900 (8°° - 17°° CET)
Email: technical-assistance@siemens.com
Internet: www.siemens.com/automation/support-request
Additional documentation
You will find further information (e.g. on parameterization,
service, etc.) in Siemens Industry Online Support
(http://support.automation.siemens.com/WW/view/en/10807
371/133300).
SIPLUS HCS3200 6BK1932-0AA00-0AA0
4 kW at 400 V AC
Class CC 15 A (internally
accessible)
25200 W
III
24 V DC (±20 %), external,
PELV
Typical: 170 mA
Max.: 250 mA
0 °C to 50 °C
-40 °C to +70°C
95 % at 25 °C, decreasing
linearly to 50 % at 50 °C
IP65
2000 m
Approx. 15 kg
300 mm x 380 mm x 200
mm
2004/108/EC
EN 61000-6-2
EN 61000-6-4
2006/95/EC
EN 61010-1
UL 508
A5E31618902A/002, 07/2014