Descargar Imprimir esta página

LG ACHH Serie Manual Del Propietario Y De Instalación página 134

Publicidad

APÉNDICE
134
• Remote desired temperature contact point table
1. Chilled Water Set Point (2 ~ 10 V, 4 ~ 20 mA)
: UI3 (Mode Cool)
500Ω
Volt [V]
[mA]
0.0
0.0
0.2
0.4
0.4
0.8
0.6
1.2
0.8
1.6
1.0
2.0
1.2
2.4
1.4
2.8
1.6
3.2
1.8
3.6
3.0
6.0
3.2
6.4
3.4
6.8
3.6
7.2
3.8
7.6
4.0
8.0
4.2
8.4
4.4
8.8
4.6
9.2
4.8
9.6
5.0
10.0
5.2
10.4
5.4
10.8
5.6
11.2
5.8
11.6
6.0
12.0
6.2
12.4
6.4
12.8
6.6
13.2
6.8
13.6
7.0
14.0
7.2
14.4
7.4
14.8
7.6
15.2
7.8
15.6
8.0
16.0
8.2
16.4
8.4
16.8
8.6
17.2
8.8
17.6
9.0
18.0
Cool Set Point
(-10 ~ 20) [°C]
No Control (Disconnect-
ed)
-10
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Cool Set Point
(14 ~ 68) [°F]
No Control (Disconnect-
ed)
14
15.8
17.6
19.4
21.2
23
24.8
26.6
28.4
30.2
32
33.8
35.6
37.4
39.2
41
42.8
44.6
46.4
48.2
50
51.8
53.6
55.4
57.2
59
60.8
62.6
64.4
66.2
68
Etc
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)