Descargar Imprimir esta página

LG ACHH Serie Manual Del Propietario Y De Instalación página 135

Publicidad

2. Hot Water Set Point (2 ~ 10 V, 4 ~ 20 mA)
: UI3 (Mode Heat)
500Ω
Volt [V]
[mA]
0.0
0.0
0.2
0.4
0.4
0.8
0.6
1.2
0.8
1.6
1.0
2.0
1.2
2.4
1.4
2.8
1.6
3.2
1.8
3.6
2.0
4.0
2.2
4.4
2.4
4.8
2.6
5.2
2.8
5.6
3.0
6.0
3.2
6.4
3.4
6.8
3.6
7.2
3.8
7.6
4.0
8.0
4.2
8.4
4.4
8.8
4.6
9.2
4.8
9.6
5.0
10.0
5.2
10.4
5.4
10.8
5.6
11.2
5.8
11.6
6.0
12.0
6.2
12.4
6.4
12.8
6.6
13.2
6.8
13.6
7.0
14.0
Heat Set Point
(30 ~ 70) [°C]
No Control
(Disconnected)
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
Heat Set Point
(86 ~ 158) [°F]
No Control
(Disconnected)
86
87.8
89.6
91.4
93.2
95
96.8
98.6
100.4
102.2
104
105.8
107.6
109.4
111.2
113
114.8
116.6
118.4
120.2
122
123.8
125.6
127.4
129.2
131
APÉNDICE
135
Etc

Publicidad

loading

Este manual también es adecuado para:

Achh020lbaa