Voltage Test With Rcd/Fi Trip Test; Continuity Test; Determining The Rotary Field Direction; Torch Light - Beha-Amprobe 2100-Alpha Manual Del Usuario

Ocultar thumbs Ver también para 2100-Alpha:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 52

Voltage Test with RCD/FI Trip Test

For voltage tests in systems with RCD/FI earth leakage
circuit breakers an RCD/FI can be tripped with a 10 mA or
30mA nominal leakage current on single phase AC 230 V
power system.
To do this, the voltage is tested between L and PE and
both pushbuttons
FI should trip.
Continuity Test (Rx)
The test circuit/object shall be
de-energized before measurement.
• Check for the absence of voltage by conducting a two-
pole voltage test on the test object
• Connect both test probes or press the pushbutton
to switch on the Tester.
• Connect both test probes to the test object. For
continuity (up to approx. 500 kΩ) the LED for
continuity Rx
• Continuity test automatically switches OFF after
approx. 30 seconds if no continuity is detected. If
continuity is detected the tester switch automatically
on.

Determining the Rotary Field Direction

The voltage testers feature a two-pole rotary field
direction detector.
Follow the safety instructions.
The rotary field direction detector is always active, the LED
may be ON constantly. However, the rotary field
6
direction can be determined only in a three-phase system
between the external conductors. The instrument displays
the voltage between two external conductors.
• Connect the handle test probe
phase L1 and the test probe
L2.
• Firmly enclose the indicator test probe around its body
!
15
If the LED
If the LED
TIP: When re-testing with exchanged test probes the
opposite result has to be occur.

Torch Light

(Measurement point illumination)
The voltage testers feature measurement point
illumination
under poor lighting conditions (e.g. distribution/control
cabinets).
To activate the torch light, press the pushbutton
measurement point illumination. Torchlight Auto power
Off off is approx. 30 seconds after last pressing the
pushbutton.

SPECIFICATIONS

Voltage Test
LED voltage range 12...690V AC/DC
LED indicator
LED tolerances
LCD voltage
range
LCD resolution
LCD tolerance
(2100-Beta only)
Frequency range
Acoustic indication ≥50 V AC, ≥120 V DC
11
are pressed simultaneously. The RCD/
7
is ON and the buzzer is active.
6
is constantly on - right rotary field
6
is constantly off - left rotary field
by a white LED. This facilitates work
4
±12, ±24, 50, 120, 230, 400, 690 V
As in EN 61243-3:2010
12...690V AC/DC
1 V
± (3% rdg + 3 LSD)
DC, 16 2/3 Hz...400 Hz
to the presumed
1
2
to the presumed phase
7
12
12
for