Room Controller for Healthcare
5.
Adjust Daylight Dimming Response*
Out-of-the-box, the daylight sensor is operational for basic operation to automatically control dimmers 1, 2 and 3. Adjustments to default
light levels are done using the Daylight Sensor Programming Remote HHPRG-RC. The remote control contains Zone Level buttons, 1, 2 and
3, which correspond to dimmers 1, 2 and 3 on the Room Controller.
When the remote is used to adjust light levels, within the daylight sensor's lens,
the Red LED should flash each time the button is pressed. The Green LED will
flash rapidly indicating that the Room Controller has entered Commissioning Mode.
Daylight levels are being set during the day when lighting should be dimming from daylight contribution, but not the the point
where loads should be at a full dim level.
Press any wallstation "All OFF" button and then turn lighting ON again. Immediately after, verify that the Green LED in the daylight
sensor lens is not ON. If it is ON, please follow the procedures to change the sensor range and reset daylight levels.
Point the remote at the daylight sensor lens and press the raise or lower button for the appropriate zone until the desired light
level is reached.
Repeat this process for each of the dimming zones as needed.
To save the new levels and exit commissioning mode, press the "All OFF" button on any wallstation. If "All OFF" is not pressed, the
controller will save the settings and exit commissioning mode after two minutes.
*Some daylighting sites may require more a in-depth setup precess due to sensor location or furnishings in the space. To
disable daylighting for a zone or if daylighting does not appear to be operating after following this basic procedure.
Advanced Daylight Level Adjustments
For more in-depth adjustments in rooms where daylighting does not seem to operate as intended with the basic daylight
setup performed, or, if the Green LED seems to be on within your daylight sensor lens, see following procedure.
Daylight levels should not be set at night or when the space is overly saturated with natural light. The daylight levels should
be set during a time when loads should be dimming from the daylight contribution, but not to the point where the load
should be at a full dim level.
www.cooperlighting.com
The setup process is now complete
Daylight Sensor
LED Location
9850-000366-04 page 14