Descargar Imprimir esta página

Cooper Lighting Solutions Greengate RC3DEHC Instrucciones De Instalación página 15

Publicidad

Idiomas disponibles

Idiomas disponibles

Greengate
Verify and Set the Daylight Sensor Range
The daylight sensor provided has three ranges of operation.
The default level is the high range of 30-3000 lux (approx.
3-280 FC) which will operate properly for most applications.
The first step in this process will be to verify the current
sensor range is adequate for the light level being sensed by
the sensor.
If the sensor is reading too much light for its current range
setting, it will flash its Green LED with a slow blink pattern
(6 seconds ON, 1 second OFF , repeated)--this blink pattern
may appear as if the Green LED is continuously ON. Adjust
the range if you see this behavior.
1.
First, identify the current programmed range for the
sensor. Point the handheld remote at the daylight
sensor lens and press the ID button on the remote. The
Sensor should flash its Red LED to indicate the current
range.
Flash Pattern
2.
Once you have determined the current range, point
the remote at the daylight sensor lens and press the
button for the new desired range level. The sensor will
acknowledge the new setting by flashing the Red LED
for the new set range.
3.
If you have adjusted the range, wait 1 minute before
making further adjustments to allow the sensor to
settle. Make sure that the Green LED is OFF before
you proceed.
Daylight Sensor
LED
Location
Reset Daylight Levels
Adjustments to default light levels are done using the
Daylight Sensor Programming Remote HHPRG-RC. The
remote control contains Zone Level buttons 1, 2 and 3
which correspond to dimmers 1, 2 and 3 on the Room
Controller.
When the remote is used to adjust light levels, within
the daylight sensor's lens, the Red LED should flash each
time the button is pressed. The Green LED will flash
9850-000366-04 page 15
October 2021
Range Information
Low Range 3-300 lux
(approx. 0-28 FC)
(Default) High Range 30-3000 lux
(approx. 3-280 FC)
Direct Sun Range 300-30000 lux
(approx. 28-2800 FC)
rapidly indicating that the Room Controller has entered
commissioning mode. To reset daylight levels and start
daylight configuration from scratch, follow the procedure
below:
1.
Ensure that daylight levels are being set during the
day when lighting should be dimming from daylight
contribution, but not to the point where loads should
be at a full dim level. be dimming from daylight
contribution, but not to the point where loads should be
at a full dim level.
2.
Reset the Room Controller's current daylight settings
by using the onboard gain adjustment dials next to the
dimmer output channels. Starting with dimmer output
1, twist the gain adjustment dial fully clockwise, then
fully counter-clockwise.
3.
Repeat this process for dimmer outputs 2 and 3.
4.
Press any wallstation "All OFF" button.
5.
Turn controlled lighting back on using the buttons
on any wallstation. Immediately after, verify that the
Green LED in the daylight sensor lens is not indicating
that the sensor is out of range. If it is ON, follow the
above procedures to change the sensor range before
proceeding.
6.
Point the remote at the daylight sensor lens and press
the raise or lower button for the appropriate zone until
the desired level is reached.
7 .
Repeat this process for each of the dimming zones as
necessary.
8.
To save the new levels and exit Commissioning
Mode, press the "All OFF" button on any wallstation.
If "All OFF" is not pressed, the controller will save
the settings and exit Commissioning Mode after two
minutes.
9.
The Room Controller will now operate with the new
daylight levels.
6
White
Switchpack
Red
Receptacle
BMS/Out
5
Black
Sensors
Green
Sensors
Slider
Station
4
Wallstations
-
A/V
Mode
+
-
3
Demand
+
Response
-
Alert
+
Mode
-
Time
Clock
+
2
1
Energy Options DIP Switch
Demand Response
Occupancy
Not Used
1
2
3
4
Default 10%
Occ
20%
Vac (default)
30%
40%
0-10V Dimming Outputs
-
-
-
+
+
+
Dimmer 3
Dimmer 2
Dimmer 1
Dimmer 3
-
Dimmer 2
-
Dimmer 1
+
+
0-10V Dimming
N
ote:
It is possible to disable daylight dimming for any
dimming zone allowing the dimmer to respond only
to the raise/lower controls and wallstation presets.
To disable daylight dimming, on the Room Controller,
twist the desired dimmer's gain adjustment dial fully
clockwise, and then fully counter clockwise. When
setting daylight levels with the HHPRG-RC remote,
avoid pressing the Zone Level adjustment buttons for
the disabled zone. If adjusted in error, simply reset
gain adjustment dial again.
Room Controller for Healthcare
Daylight Gain
Adjustment
Dimmer 3
-
Dimmer 2 Dimmer 1
-
-
+
+
+
0-10V Dimming
-
+
www.cooperlighting.com

Publicidad