Descargar Imprimir esta página

Grundfos UNOLIFT Instrucciones De Instalación Y Funcionamiento página 18

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 134
4. Starting up the product
4.1 Starting up a product with a controller
Make sure that the controller is set correctly. See
section
3.20 Setting the controller before
1. Make sure that all pipes and connections are
tight.
2. Switch on the controller.
3. Set the selector switch to "AUTO".
4. Open the isolating valves.
5. Flush a toilet or open a tap connected to one of
the inlets.
6. Monitor the increasing liquid level in the tank up
to the start level and check that the pumps start
and stop at least twice.
4.2 Starting up a product without a
controller
1. Make sure that all pipes and connections are
tight.
2. Open the isolating valves.
3. Switch on the power supply to the pump.
4. Flush a toilet or open a tap connected to one of
the inlets.
5. Monitor the increasing liquid level in the tank up
to the start level and check that the pumps start
and stop at least twice.
5. Storing the product
CAUTION
Back injury
Minor or moderate personal injury
- Get assistance from another person or
use lifting equipment to carry the
product.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes when moving the
product.
The tank must not be exposed to direct sunlight. UV
light can affect the properties of its composite
material, resulting in a shorter life.
For information on how to store the pumps and the
controller, see the installation and operating
instructions of the product.
18
6. Product introduction
6.1 Product overview
startup.
Fig. 22
Fig. 23
Pos.
1
2
3
4
5
6
7
8
Unolift 270 / Duolift 270
Duolift 540
Description
Horizontal main inlets, DN 100
Mounting brackets
Connection, DN 40, for optional
diaphragm pump
Pump outlet
Holes for cable glands
Outlet for vent pipe, ∅60
Vertical main inlet, DN 100
Hole for level sensor hose

Publicidad

loading

Este manual también es adecuado para:

Duolift