Ensure the correct polarity is maintained throughout all wiring. Otherwise, it will cause electrical shock or fi re.
After installation, check the water leakage condition in connection area during test run. If leakage occurs, it will cause damage to other properties.
If the Tank Unit not operates for long time, the water inside the Tank Unit should be drained.
Installation work.
It may need three or more people to carry out the installation work. The weight of Tank Unit might cause injury if carried by one person.
PRECAUTION FOR USING R32 REFRIGERANT
•
The basic installation work procedures are the same as conventional refrigerant (R410A, R22) models.
However, pay careful attention to the following points:
When connecting fl are at indoor side, make sure that the fl are connection is used only once, if torqued up and released, the fl are must be remade.
Once the fl are connection was torqued up correctly and leak test was made, thoroughly clean and dry the surface to remove oil, dirt and grease by
following instructions of silicone sealant. Apply neutral cure (Alkoxy type) & ammonia-free silicone sealant that is non-corrosive to copper & brass to the
external of the fl ared connection to prevent the ingress of moisture on both the gas & liquid sides. (Moisture may cause freezing and premature failure
of the connection)
The appliance shall be stored, installed and operated in a well ventilated room with comply to Indoor Floor Area Requirement and without any
continuously operating ignition source. Keep away from open fl ames, any operating gas appliances or any operating electric heater. Else, it may
explode and cause injury or death.
Refer to "PRECAUTION FOR USING R32 REFRIGERANT" in outdoor unit installation manual for other precautions that need to pay attention to.
INDOOR FLOOR AREA REQUIREMENT
•
If the total refrigerant charge in the system is <1.84 kg, no additional minimum fl oor area is required.
If the total refrigerant charge in the system is ≥1.84 kg, additional minimum fl oor area requirements is complied as described below:
•
Symbol
Description
m
Total refrigerant charge in system
c
m
Maximum refrigerant charge allowed
max
m
m
- m
excess
c
max
H
Installation height
VA
Minimum ventilation opening area
min
A) Determine Maximum refrigerant charge allowed, m
1. Calculate Installation Room Area, A
2. Based on Table I, select m
3. If m
> m
, the unit can be installed in the installation room with
max
c
the specifi ed installation height ( H=600mm ) in Table I and without additional room area or any additional ventilation.
4. Else, proceed to B) and C).
B) Determine Total Floor Area of A
1. Calculate the B
area adjacent to the A
room
2. Determine the A
based on the Total Refrigerant Charge, m
min total
3. The total fl oor area of both A
C) Determine Minimum Venting Opening Area, VA
1. From Table III, calculate m
2. Then determine VA
corresponding to the calculated m
min
for natural ventilation between A
3. The unit can be installed at specifi c room only when the following conditions are fulfi lled:
•
Two permanent openings (cannot be closed), one at bottom, another at top, for ventilation purposes are made between
A
and B
.
room
room
•
Bottom opening: - Must comply to the minimum area requirement of VA
- Opening must be located 300mm from the fl oor.
- At least 50% of required opening area must be 200mm
from the fl oor.
- The bottom of the opening shall not be higher than the
point of release when the unit is installed
and must be situated 100mm above the fl oor.
- Must be as close as possible to the fl oor and lower than H .
•
Top opening:
- The total size of the Top opening must be more than
50% of VA
- Opening must be located 1500mm above the fl oor.
•
The height of the openings must more than 20mm.
•
A direct ventilation opening to outside is NOT encouraged for ventilation opening (the user can block the opening when it is cold).
•
The value of H is considered as 0.6m to comply to IEC 60335-2-40:2018 Clause GG2.
Unit
max
.
room
which corresponds to the calculated A
max
and B
compliance to A
room
room
.
room
and B
must exceed A
room
room
for natural ventilation
min
.
excess
and B
.
room
room
.
min
kg
kg
Total refrigerant charge in system, m
kg
= Pre-charged refrigerant amount in unit (kg)
m
+ Additional refrigerant amount after installation (kg)
2
cm
value.
room
min total
from Table II.
c
.
min total
excess
.
min
(kg)
c
Installation
Room
Adjacent
( A
)
Room
room
( B
)
room
>0.5 VA
min
> VA
min
3