Descargar Imprimir esta página

Hitachi RCI1.0FSN3Ek Manual De Instalación Y Funcionamiento página 13

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 23
Electrical wiring
5.2 DRAIN PIPE CONNECTION
1 The position of the drain pipe connection is shown below.
Common drain piping
2 Prepare a polyvinyl chloride pipe with a 32mm outer diameter.
3 Fasten the tubing to the drain hose with an adhesive and the
factory-supplied clamp. The drain piping must be performed
with a down-slope pitch of 1/25 to 1/100.
4 Do not apply excessive force to the drain pipe connection. It
could cause a damage.
5 Do not use a bent or twisted drain hose. It will cause water
leakage.
Gradient of Drain piping
6 ELECTRICAL WIRING
6.1 GENERAL
D A N G E R
Turn off the main power switch to the indoor unit and the
outdoor unit before electrical wiring work or a periodical
check is performed.
Check to ensure that the indoor fan and the outdoor fan
have stopped before electrical wiring work or a periodical
check is performed.
Protect the wires, drain pipe, electrical parts, etc. from
rats or other small animals. If not protected, rats may
gnaw at unprotected parts and at the worst, a fire will oc-
cur.
C A U T I O N
Use twisted shielded pair cable or shield pair cable for trans-
mission wires between the indoor and the outdoor units, and
connect the shielded part to the earth screw in the electrical
box of the indoor unit as shown below.
Wrap the field supplied insulation around the wires, and plug
the wiring connection hole with the seal material to protect the
product from any condensate water or insects.
Tightly secure the wires with the cord clamp inside the indoor
unit.
Lead the wires through the knockout hole in the side cover
when using conduit.
Secure the cable of the remote control switch using the cord
clamp inside the electrical box.
11
PMML0280A rev.1 - 09/2014
6 Insulate the drain pipe after connecting the drain hose. Do
1/25~1/100
Down slope

1 Make sure that the field-selected electrical components (main
2 Check to ensure that the power supply voltage is within +10%
3 Check the capacity of the electrical wires. If the power source
4 Check to ensure that the ground wire is connected.
not use adhesive between the drain pipe connection and the
drain hose.
Hose Band (Accessory)
Do not use adhesive
Drain pipe connection
Drain hose
(Accessory)
Hose band (Accessory)
Insulation (Field supplied)
General Check
 
power switches, circuit breakers, wires, conduit connectors
and wire terminals) have been properly selected. Make sure
that the components comply with National Electrical Code
(NEC).
of the rated voltage.
capacity is too low, the system cannot be started due to the
voltage drop.
Vinyl Chloride VP25
(Field Supplied)
Use Vinyl Chloride type adhesive

Publicidad

loading

Este manual también es adecuado para:

Rci-6.0fsn3ekP-ap160na1P-ap160nae