PEDROLLO TISSEL-100 Instrucciones Originales De Uso página 31

Variador electrónico de frecuencia

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 40
SETTING THE BASIC PARAMETERS)
It is imperative the BASIC PARAMETERS for the configuration of the inverter are set during the installation.
BASIC
DISPLAY
PARAMETERS
SET PRESSURE
P 3.5
(bar)
SECOND SET
2P 2.5
PRESSURE
(bar)
MOTOR CURRENT (A) Sets the nominal current of the motor on exit from the inverter (current of the motor
A 6.0
DIRECTION OF
RO >
ROTATION OF THE
MOTOR
(only models with a
three-phase outlet)
DESCRIPTION
Sets the value of the constant
pressure in the plant.
Sets a second pressure value.
To activate it the EI parameter must be
configured in the advanced parameters
– see name plate).
In the presence of a low network voltage the current set must take into
consideration a margin (eg. 15%) which compensates for the low voltage.
ONLY PRESENT FOR A THREE-PHASE OUTLET - Sets the direction of rotation of the
three-phase motor (clockwise or anti-clockwise)
u.m. Default Min
Max
bar
3.5
1
10
psi
50
15
130
bar
2.5
1
10
psi
50
15
130
ENGLISH |
Step
0.1
1.5
0.1
1.5
31