Basic wiring diagram
Connect the inter-unit control wiring as shown in the fi gure.
When connecting interface adaptor, read the installation instructions supplied with
each product.
Power Source
ON/OFF Controller
100-240V ~
N
L
Power suply
wiring
Schedule Timer wiring
This unit
Signal terminal
Power supply
board
terminal board
100-240V
FG
FG
How to attach the ring pressure terminal
For power supply wiring
• Process the end of each wiring and attach the
ring pressure terminal (fi eld supplied item).
For shield wiring
• Process the end of the each wiring and attach the ring pressure terminal
(fi eld supplied item).
Remove wiring coat.
Cover with the tape.
Attach ring pressure
terminal.
Attention
Ground the shield on both sides of shield wiring,
ohterwise an operation error from noise may occur.