Tariffs
Tariff for back-up boiler:
Electricity tariff type:
Single tariff
High tariff:
Dual tariff
Dual tariff weekly planner
Low tariff:
Offset
Room temperature: K
Outdoor temperature: K
Factory settings
2.14.4
Installation configuration menu item
MENU | SETTINGS | Installer level
Installation configuration
Installation
Water pressure: bar
eBUS components
Adaptive heat curve:
Automatic cooling:
Outdoor temp., 24 hr av.: °C
Cooling at outdoor temp.: °C
Source regeneration:
Current room air humidity: %rel
Current dew point: °C
Hybrid manager:
triVAl
0020287900_03 Operating and installation instructions
The hybrid manager uses the tariffs and the heat demand to calcu-
late the costs for the back-up boiler and the heat pump. The more
cost-effective component is used for the heat generation.
Enter a gas, oil or electricity tariff. The tariff must refer to the same
unit of measurement as the electricity tariff for the heat pump, e.g.
ct/kWh.
Applies only for heat pumps
The costs are always calculated using the high tariff.
The costs are calculated using the high and low tariffs.
Up to twelve time periods can be set per day
The High tariff: applies within the time periods.
The Low tariff: applies outside of the time periods.
Comparison of the temperature difference between the measured
value in the system control and the value for a reference thermo-
meter in the living room.
Comparison of the temperature difference between the measured
value in the outdoor temperature sensor and the value for a refer-
ence thermometer in the living room.
The system control resets all of the settings to the factory settings
and calls up the installation assistant.
Only the competent person can operate the installation assistant.
Current water pressure in the heating installation
List of eBUS components and their software versions
Automatic fine adjustment of the heat curve. Prerequisite:
The suitable heat curve for the building is set in the Heat
curve: function.
The correct zone is assigned to the system control or the
remote control in the Zone assignment: function.
Expanded is selected in the Room temp. mod.: function.
Factory setting: Deactivated
When a heat pump is connected, the system control automatically
switches between heating mode and cooling mode.
Factory setting: Deactivated
Outdoor temperature averaged over the last 24 hours. The value is
used by the Automatic cooling: function.
Cooling starts once the outdoor temperature (24-hour average)
exceeds the set temperature.
Factory setting: 15 °C
The system control switches the Cooling function on and guides
the heat from the living room back to the earth via the heat pump.
Prerequisite:
The Automatic cooling: function has been activated.
The Absence function is active.
Factory setting: No
Current room air humidity, measured using the installed humidity
sensor
The system control calculates the current dew point in the living
room.
Factory setting: Bival. point
The heat generator is selected based on the set tariffs in relation
to the heat demand.
67