NOTE
If cabinet has a drawer, a minimum 127 mm (5") depth clearance from the top of
Countertop to top of the drawer (or other obstruction) in base cabinet is required.
IMPORTANT:
The junction box must be located where it will allow considerable slack in the
conduit for serviceability.
Electrical requirements
WARNING
Electrical Shock Hazard
Disconnect power before servicing.
Use 8 gauge solid copper wire.
Electrically ground cooktop.
Label
Label
• Refer the label on the bottom
or front of the cooktop for
power requirements and model
information.
This cooktop must be connected to a grounded metal, permanent wiring system.
Be sure that the electrical connection and wire size are adequate and in
conformance with the National Electrical Code, ANSI/NFPA 70-latest edition or CSA
Standards C22.
1-94, Canadian Electrical Code, Part 1 and C22.2 No. O-M91-latest edition, and all
local codes and ordinances.
A copy of the above code standards can be obtained from:
DTI36P876BB,DTI30P876BB_DG68-01292A-00_EN+MES+CFR.indb 7
Failure to follow these instructions can
result in death, fire, or electrical shock.
If codes permit and a separate ground
wire is used, it is recommended that a
qualified electrical installer determine that
the ground path and the wire gauge are in
accordance with local codes.
Check with a qualified electrical installer if
you are not sure the cooktop is properly
grounded.
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
178 Rexdale Boulevard,
Toronto, ON, Canada M9W 1R3
Before you make the electrical connection:
To properly install your cooktop, you must determine the type of electrical
connection you will be using and follow the instructions provided for it here.
• A 3-wire or 4-wire, single phase, 208 or 240 volt AC, 60-Hz, power supply is
required on a dedicated double pole circuit breaker of at least 40 amps for the
30" cooktop, and of at least 45 amps for the 36" cooktop.
NOTE
• The cooktop is rated 240 volt. Some models have a neutral (white) wire.
• The cooktop should be connected directly to the junction box through flexible,
armored or nonmetallic sheathed, copper cable. The flexible, armored cable
extending from the fuse box or circuit breaker box should be connected directly
to the junction box.
• Locate the junction box to allow as much slack as possible between the junction
box and the cooktop so that the cooktop can be moved if servicing becomes
necessarry in the future.
• Do not cut the conduit. Use the length of conduit provided.
• A UL listed or CSA approved conduit connector is necessary at each end of the
power supply cable (at the cooktop and at the junction box). A listed conduit
connector is already provided at the cooktop.
• If the house has aluminum wiring, follow the procedure below:
1. Connect a section of solid copper wire to the pigtail leads.
2. Connect the aluminum wiring to the added section of copper wire using
special connectors and/or tools designed and UL listed for joining copper
to aluminum.
Follow the electrical connector manufacturer's recommended procedure.
Aluminum/copper connection must conform with local codes and industry
accepted wiring practices.